Plan Review Notes
Plan Review Notes For Project Z19080025
Project Number Z19080025
Review Stop Z
Sequence Number 3
Notes
Date Text
2020-02-26 10:08:50*** COMMENTS PROVIDED IN ADDITION TO ZONING REVIEW
 DATED 2/18/20 ***
  
 GENERAL COMMENTS:
  
 1.) A TRAFFIC PERFORMANT STANDARDS (TPS) REVIEW LETTER
 FROM THE PALM BEACH COUNTY DEPARTMENT OF ENGINEERING -
 TRAFFIC DIVISION, INDICATING THAT THE PROJECT MEETS THE
 TPS STANDARDS OF THE COUNTY IS REQUIRED.
  
 2.) WHERE IS THE SURVEYOR GETTING THE LEGAL DESCRIPTION
 FROM? THE LEGAL DOES NOT SEEM TO BE ACCURATE (I.E.
 BLOCK REFERENCE, PLAT BOOK AND PAGE NUMBER REFERENCE,
 ETC.). PLEASE ADDRESS FOR CONSISTENCY.
  
 3.) WHAT IS THE GENERAL TIMELINE OF CONSTRUCTION FOR
 BOTH PHASE I AND PHASE II?
  
 4.) ANY CHANGES TO THE PROJECT DATA TABLE (SHEET A1.0)
 SHALL BE MADE CONSISTENT WITH THE CHANGES TO THE
 PROJECT DATA TABLE ON THE COVER SHEET AND IN THE TABLES
 IN THE PHASING SITE PLAN (SHEET A1.1).
  
 5.) A SIDEWALK EASEMENT FOR THE 3 FT. SIDEWALK
 ENCROACHMENT ONTO PRIVATE PROPERTY SHALL BE REQUIRED
 PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 (C.O.).
  
 6.) TO DATE, THE SIGNED LETTER FROM THE OLD NORTHWOOD
 HISTORIC DISTRICT NEIGHBORHOOD ASSOCIATION HAS NOT BEEN
 RECEIVED.
  
  
 SITE PLAN COMMENT:
  
 1.) SURFACE PARKING AREA SHALL BE CONCEALED WITH A
 STREET WALL ALONG ALL STREET FRONTAGES. [ZLDR
 S.94-220(F)(3)] [11/7/19 REPEAT COMMENT - PER ZLDR
 S.94-219(C), THE APPLICANT MAY SEEK A WAIVER FROM THIS
 DESIGN STANDARD TO BE APPROVED BY THE ZONING BOARD OF
 APPEALS.]
  
 2.) OPEN-AIR PORCHES AND STOOPS, STAIRS AND RAMPS MAY
 ENCROACH INTO ANY REQUIRED SETBACK TO A POINT NOT
 CLOSER THAN 3 FT. TO THE PROPERTY LINE. THE PROJECT
 DOES NOT COMPLY WITH THE STANDARD. PLEASE ADDRESS.
 [ZLDR S.94-220(B)(5)] [11/07/19 REPEAT COMMENT -
 ALTHOUGH THE STEPS ALONG BROADWAY HAVE BEEN MODIFIED TO
 MEET CODE, THE RAMP ALONG THE SOUTH SIDE OF THE
 PROPERTY STILL SEEMS TO ENCROACH INTO THE REQUIRED 3
 FT. SETBACK]
  
 3.) RAMP DETAIL PROVIDED ON SHEET A1.2 SHALL BE
 MODIFIED TO MATCH ANY CORRECTION MADE WITH THE
 PLACEMENT/LOCATION IN THE SITE PLAN.
  
 4.) WHAT IS THE COMBINED HEIGHT OF THE METAL PICKET
 FENCE AND THE RETAINING WALL ALONG THE NORTH PROPERTY
 LINE? THE FENCE/WALL CANNOT EXCEED 6 FT. IN HEIGHT
 (OVERALL). ALSO, PROVIDE A DETAIL TO DEMONSTRATE
 COMPLIANCE. [ZLDR S.94-220(D)(2) AND (3)] [11/7/19
 REPEAT/MODIFIED COMMENT]
  
 5.) DETAIL OF THE FENCE/GATE ON BROADWAY IS MISSING.
 PLEASE PROVIDE. [11/7/19 REPEAT/MODIFIED COMMENT -
 ALTHOUGH RESPONSES TO STAFF'S COMMENTS IMPLIES THAT A
 DETAIL HAD BEEN PROVIDED, IT SEEMS TO BE MISSING FROM
 THE PLAN.]
  
 6.) METAL PICKET FENCE IN THE BUILDING ELEVATIONS DO
 NOT MATCH THE DETAIL PROVIDED ON SHEET A1.2. PLEASE
 ADDRESS FOR CONSISTENCY.
  
 7.) ACCORDING TO THE CIVIL PLANS, A LIGHT POLE FIXTURE
 ALONG BROADWAY WILL BE RELOCATED. THIS SHOULD BE
 REFERENCED IN ALL OTHER PLANS FOR CONSISTENCY. ALSO,
 NOTE THAT THE LOCATION OF THE "EXISTING" POLE FIXTURE
 IS INCONSISTENT (I.E. SHIFTED). ADDRESS FOR
 CONSISTENCY.
  
 8.) PARKING STALL STRIPING DETAIL SHALL BE CONSISTENT
 WITH THE CITY'S STALL STRIPING STANDARDS PER ZLDR
 S.94-485. THE DETAIL PROVIDED ON SHEETS A1.2 AND PD6 IS
 INCONSISTENT WITH THE CITY'S STANDARDS.
  
 9.) FOLLOWING CORRECTIONS IN THE PROJECT DATA TABULAR
 REQUIRED: A) CHECK THE LEGAL DESCRIPTION. IT SEEMS TO
 BE INCORRECT (SEE GENERAL COMMENTS NOTE ON SURVEY); B)
 CHECK LOT COVERAGE AND BUILDING SQUARE FOOTAGE
 CALCULATIONS (THE NUMBERS SEEM TO BE OFF); C) SHOW THAT
 THE MAXIMUM FRONT SETBACK ALONG BROADWAY IS 15 FT. (NOT
 5 FT.); D) CHECK UNIT CALCULATIONS IN THE RESIDENTIAL
 DENSITY BREAKDOWN (PHASE I COUNT IS INCORRECT).
  
 10.) COVER PAGE TITLE STATES THAT THE PROJECT IS A "24
 RESIDENTIAL UNIT DEVELOPMENT" (NOT 23). PLEASE CORRECT
 FOR CONSISTENCY.
  
  
 ARCHITECTURAL (FLOOR PLAN AND ELEVATIONS) COMMENTS:
  
 1.) FLAT ROOFS SHALL BE ENCLOSED BY A PARAPET NO LESS
 THAN 42 INCHES IN HEIGHT. PLEASE DEMONSTRATE COMPLIANCE
 BY PROVIDING DIMENSIONS IN THE ELEVATIONAL DRAWINGS.
 [ZLDR S.94-220(D)(9)] [11/7/19 - REPEAT COMMENT - PER
 ZLDR S.94-219(C), THE APPLICANT MAY SEEK A WAIVER FROM
 THIS DESIGN STANDARD TO BE APPROVED BY THE ZONING BOARD
 OF APPEALS.]
  
  
 INSTRUCTIONS FOR RESUBMITTAL:
  
 * PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF TWELVE
 (12) PAPER COPIES, ONE (1) REDUCED COPY IN 8.5 INCHES X
 11 INCHES AND ONE (1) SET IN 11 INCHES X 17 INCHES, AND
 AN ELECTRONIC COPY OF ALL PLANS.
  
 * PLEASE NOTE THAT CHANGES ON THE RESUBMITTED PLANS MAY
 RESULT IN ADDITIONAL COMMENTS.
  
 * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE
 ($200.00).
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  