2020-02-28 17:51:47THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 FEBRUARY 21, 2020 SUBMITTAL REVIEW SET:
  
 1. PRB'S ARE GENERALLY ARE NOT NEEDED IN A MANHOLE IF
 THE INLET STRUCTURES UPSTREAM FROM THE MANHOLE HAVE
 PRB'S. FOR EXAMPLE, MANHOLE STRUCTURES #103 AND #104
 WILL NOT NEED PRBS BECAUSE CATCH BASIN STRUCTURES #201
 AND #102 WILL HAVE PRB'S. .
  
 2. EXPLAIN HOW THE PERIMETER WALL ELEVATION OF 17.25
 WAS DETERMINED WHEN 25-YEAR 72-HOUR PEAK STAGE IS
 LISTED AS 17.60.
  
 3. VERIFY THE PEAK STAGES (PRE- AND POST-DEVELOPMENT)
 FOR THE 25-YEAR 3-DAY AND 100-YEAR 3-DAY DESIGN STORMS.
 THE 25-YEAR PEAK STAGES ARE SHOWN TO BE HIGHER THAN THE
 100-YEAR PEAK STAGES.
  
 4. THE SITE PLAN SHOWS SQUARE CORNERS FOR THE CURBING
 AT THE NORTH END OF THE PARKING LOT BUT THE ENGINEERING
 PLANS SHOW ROUNDED CURBING.
  
 5. ADJUST THE ORIENTATION OF THE SITE LIGHT FIXTURE
 NEXT TO THE CURB OPENING FOR DRAINAGE AT THE NORTH END
 OF THE PARKING LOT ON THE ENGINEERING PLANS. THE SITE
 PLAN SHOWS THE LIGHT OVER THE PARKING LOT.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT