2019-09-10 09:01:091. ADD CONVERSION TO NGVD-29 ON ALL PLANS.
 2. WHY ARE INVERT ELEVATIONS CROSSED OUT ON SURVEY?
 3. LEICA GPS IS NOT AN ORIGINATING BENCHMARK. SHOULD BE
 LABELED AS BOUNDARY & TOPOGRAPHIC SURVEY.
 4. DUMPSTER DOORS CANNOT OPEN INTO ALLEY.
 5. PHASE 1 PARKING LANES DURING CONSTRUCTION APPEAR TO
 BE AN UNSAFE DRIVEWAY CONDITION.
 6. ALL DETAILS NEED TO BE PER CITY OF WEST PALM BEACH.
 7. RECOMMEND APPLICANT MEET WITH TRAFFIC AND
 ENGINEERING.
 8. PLEASE REFER TO ENGINEERING CHECKLIST IN THE
 DEVELOPMENT APPLICATION FOR REQUIRED INFORMATION PRIOR
 TO RE-SUBMITTAL.