| 2020-02-18 07:28:46 | 1. SHEETS 3 & 4 ? PLEASE CORRECT SPELLING OF |
| | ?DEMOLITION? ON PAGE TITLE. |
| | 2. SHEET 8 ? PLEASE SHOW INLET / DRAINAGE STRUCTURE |
| | POLLUTION PROTECTION. |
| | 3. SHEET 9 ? PLEASE CLEARLY IDENTIFY EXISTING WATER |
| | MAIN DETAILS ON DIXIE HWY. AND BANYAN BL. ? MATERIAL, |
| | SIZE, VALVES ETC. |
| | 4. SHEET 9 ? PLEASE REALIGN WATER TAP TO BE PARALLEL |
| | FROM EXISTING WATER LINE( I.E. NO BENDS IF POSSIBLE). |
| | 5. SHEET 9 ? PLEASE LABEL BANYAN BL. |
| | 6. SHEET 9 ? PLEASE CLEARLY LABEL RIGHT OF WAY. |
| | 7. SHEET 10 ? PLEASE CLEARLY IDENTIFY EXISTING WATER |
| | MAIN DETAILS ON DIXIE HWY. AND BANYAN BL. ? MATERIAL, |
| | SIZE, VALVES ETC. |
| | 8. SHEET 10 ? PLEASE CLEARLY LABEL RIGHT OF WAY. |
| | 9. FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES |
| | OF WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS. |
| | 10. FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING |
| | APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT |
| | SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING |
| | SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED |
| | LEAD-FREE DESIGN. |
| | 11. FOR FORMAL ENGINEERING SUBMITTAL, IF SANITARY LINES |
| | ARE PROPOSED IN ROW PLEASE SHOW ADJACENT SANITARY |
| | LATERAL LOCATIONS AND SHOW ADDRESSES OF ADJACENT |
| | PARCELS. |
| | 12. FOR FORMAL ENGINEERING SUBMITTAL, IF WATER LINES |
| | ARE BEING REPLACED IN ROW, SHOW ADJACENT PARCEL |
| | ADDRESSES. |
| | 13. FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING |
| | APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT |
| | SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING |
| | SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED |
| | LEAD-FREE DESIGN. |
| | 14. FOR FORMAL ENGINEERING SUBMITTAL PROVIDE SANITARY |
| | ELEVATIONS AT MANHOLE TIE-IN. |
| | 15. FOR FORMAL ENGINEERING SUBMITTAL, IF SANITARY LINES |
| | ARE PROPOSED IN ROW PLEASE SHOW ADJACENT SANITARY |
| | LATERAL LOCATIONS AND SHOW ADDRESSES OF ADJACENT |
| | PARCELS. |
| | 16. FOR FORMAL ENGINEERING SUBMITTAL, IF WATER LINES |
| | ARE BEING REPLACED IN ROW, SHOW ADJACENT PARCEL |
| | ADDRESSES. |
| | 17. PLEASE RESPOND TO ALL COMMENTS IN WRITING. |
| | |
| | COMMENTS BELOW PER MARK HURLEY, PUBLIC UTILITIES |
| | CUSTOMER SERVICE SUPERVISOR, [email protected] |
| | |
| | 18. -DETAIL A ON SHEET 9 DOES NOT HAVE ENOUGH DETAIL. |
| | METER & BACKFLOW SIZES NEEDS TO BE DETERMINED AND |
| | LABELED AS THE SPACE REQUIREMENT CAN BE SUBSTANTIALLY |
| | DIFFERENT BETWEEN SIZES. SHOWING 15FT UE RUNNING N-S, |
| | BUT MAY NEED GO E-W WITH A LARGER METER. NEED REFERENCE |
| | THE APPROPRIATE WS SD # ON EACH LABEL. IF DOMESTIC |
| | METER IS 3 IN. OR LARGER IT NEEDS TO BE ABOVE-GROUND |
| | VIA WS-8 (ALSO LABEL AS DOMESTIC). NEED A POINT OF |
| | SERVICE GATE VALVE FOR FIRELINE AFTER THE BRANCH AT THE |
| | PROPERTY LINE AND LABEL IT. PIPE MATERIAL AFTER 8 |
| | IN.TAP NEED BE LABELED. THERE IS A GATE VALVE ICON FOR |
| | THE ?R.P.B.A? AND SHOULD BE REPLACED WITH BACKFLOW |
| | ASSEMBLY ICON. |
| | 19. -DEMAND CHART DOES NOT SHOW IRRIGATION. WILL THERE |
| | BE ANY IRRIGATION USE? |
| | 20. -ON SHEET 10, EXISTING WATER MAIN NOT LABELED WITH |
| | PIPE MATERIAL. DCDA SIZE NEEDS TO BE DETERMINED AS MAY |
| | NOT NEED 8 IN. TAP IF SMALL SIZED DCDA (ALSO LABEL WITH |
| | WS SD# REFERENCE). FIRELINE BACKFLOW ASSEMBLY AND |
| | ASSOCIATED PIPING APPEARS TO BE LOCATED OUTSIDE OF |
| | PROPERTY LINE -> SHOULD BE LOCATED INSIDE PROPERTY LINE |
| | (SHIFT WEST). |
| | 21. -ON SHEET 10, IS 10 FT SQUARE UTILITY EASEMENT |
| | EXISTING? IF NOT, WHY IS IT BEING CREATED? IF NOT |
| | REQUIRED, THEN MAY BE POSSIBLE TO ELIMINATE/REDUCE AND |
| | SHIFT DCDA SOUTH SOME. |
| | 22. -ON SHEET 10 REQUEST POINT OF SERVICE VALVE TO BE |
| | RELOCATED SLIGHTLY NORTH OUT OF PAVER WALKWAY AND INTO |
| | GRASS. |
| | |
| | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR |
| | CONCERNS, THANKS. |
| | RICK ROSSANO, PROJECT COORDINATOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | DIRECT: (561) 494-1098 [email protected] |
| | |
| |