| 2020-03-24 09:31:04 | THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE MARCH |
| | 17, 2020 REVIEW SUBMITTAL PACKAGE. THESE COMMENTS CAN |
| | BE ADDRESSED DURING THE ENGINEERING PERMIT SUBMITTAL. |
| | |
| | 1. CONFIRM THE SIZE OF THE EXISTING STORMWATER PIPE IN |
| | BANYAN BLVD BETWEEN N. DIXIE HIGHWAY AND THE MANHOLE IN |
| | FRONT OF THE BANK DRIVE-THROUGH TELLER LANES IS 48" OR |
| | 42". CONTACT JANICE TARBILL IN THE ENGINEERING SERVICES |
| | DEPARTMENT FOR AS-BUILT PLANS. |
| | |
| | 2. ON THE DEMOLITION PLAN SHEET, SHOW THE REMOVAL OF |
| | THE EASTERN PARKING SPACE NEAR THE DRIVEWAY ENTRANCE TO |
| | N. OLIVE AVE. |
| | |
| | 3. SHEET 9 OF 10 CALLS OUT A NON-STANDARD STORMWATER |
| | PIPE SIZE (16") IN THE CONFLICT NOTE WITH THE WATER |
| | MAIN ON N. DIXIE HIGHWAY. |
| | |
| | 4. SHOW SILT FENCE AT THE PROPERTY LINE/BACK OF |
| | SIDEWALK OR CURB ON THE POLLUTION PREVENTION PLAN. THE |
| | SILT FENCE WILL BE NEEDED DURING DEMOLITION AND UNTIL |
| | THE BUILDING WALLS AND SIDEWALKS ARE COMPLETED. |
| | |
| | 5. CALL OUT THE HIGH POINT IN THE DRIVE AISLE/DRIVEWAY |
| | TO BANYAN BLVD AND HAVE IT AS CLOSE TO THE BACK OF |
| | SIDEWALK AS POSSIBLE. |
| | |
| | 6. CONFIRM THE DRAINAGE INLETS IN THE DRIVE AISLE WILL |
| | BE CONCRETE STRUCTURES (TYPE 'E') AND NOT YARD DRAINS |
| | AS LABELED ON THE LANDSCAPE PLAN. |
| | |
| | 7. COORDINATE THE LOCATION OF THE YARD DRAIN IN THE |
| | PUBLIC OPEN SPACE WITH THE PLACEMENT OF LANDSCAPING AND |
| | SCULPTURES. THE GARDEN COURTYARD LANDSCAPE PLAN (SHEET |
| | LP.2) SHOWS THE PLACEMENT OF A SCULPTURE ON TOP OF THE |
| | YARD DRAIN. |
| | |
| | 8. THE AREA BETWEEN THE BUILDING AND THE NORTH PROPERTY |
| | LINE WILL NEED GROUND COVER AT THE END OF CONSTRUCTION |
| | TO PREVENT EROSION AND SEDIMENT MIGRATION OFFSITE. |
| | |
| | 9. PROVIDE PROFILE OF STORM PIPE BETWEEN STORMCEPTOR |
| | AND PROPOSED STORM MANHOLE IN BANYAN BLVD. SHOWING ALL |
| | OF THE UTILITIES CROSSING THE PROPOSED STORM PIPE. |
| | |
| | TRACY WARD, P.E. |
| | SENIOR STORMWATER ENGINEER |
| | ENGINEERING SERVICES DEPARTMENT |