Plan Review Notes
Plan Review Notes For Project Z19080020
Project Number Z19080020
Review Stop ENG - PPRC
Sequence Number 2
Notes
Date Text
2019-11-25 15:35:151) PLEASE SHOW NAVD 1988 TO NGVD 1929 CONVERSION ON ALL
 SHEETS.
 2) PLEASE SHOW CONFLICTS AT UTILITY CROSSINGS IN RIGHT
 OF WAY.
 3) PLEASE CLEARLY SHOW ENLARGED DETAIL OF AREA WITH
 PLACEMENT OF BACKFLOWS AND METERS, AND COORDINATE WITH
 MARK HURLEY OF PUBLIC UTILITIES CUSTOMER SERVICE AT
 [email protected] OR 561-822-2262.
 4) PLEASE CLEARLY SHOW ENLARGED DETAIL OF AREA OF
 PROPOSED MANHOLE ADJACENT TO COMMUNICATIONS VAULT.
 5) PLEASE LABEL BACKFLOWS PER MARKUP (RPPA, DCDA).
 6) PLEASE PROVIDE 15 FT. EASEMENT OVER METER PER
 MARKUP.
 7) PLEASE PROVIDE DETAILS ON PROPOSED TAPS (VALVES,
 ETC.).
 8) PLEASE LABEL ALL CITY POINTS OF SERVICE.
 9) PLEASE SHOW SECOND TAP ON DIXIE HWY. PER MARKUP
 (KEEP WATER SOURCE AS CLOSE AS POSSIBLE).
 10) PLEASE CALL OUT PAVEMENT RESTORATION PER CITY OF
 WPB STANDARD DETAIL GC-9.
  
 FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD CUSTOMER
 SERVICE SUPERVISOR IN PUBLIC UTILITIES.
 [email protected], 561-822-2240.
  
 -SOUTHERN U.E. LOOKS TO EXTEND TOO FAR SOUTH ? SHOULD
 JUST BE WITHIN PROPERTY LINES.
  
 -EXISTING WATER UTILITIES ARE NOT LABELED WITH WHAT IS
 HAPPENING TO THEM. FOR EXAMPLE -> SMALL WATER SERVICE,
 METER & BOX ADJACENT SOUTHERN DCDA AND THE FIRE HYDRANT
 ON WEST SIDE.
  
 - ?THE BACKFLOW OFF OF DIXIE IS PROPOSED TO BE MOUNTED
 ON THE INSIDE OF THE GARAGE ENTRANCE? -> FIRELINE
 BACKFLOW ASSEMBLIES SHOULD NOT BE INSIDE BUILDINGS
 UNLESS FIRE DEPARTMENT IS REQUIRING THEM TO BE INSIDE.
 ALSO LIKE THEM TO BE HORIZONTAL AND SUPPORTED SIMILAR
 TO THE STANDARD DETAIL, AND OUT OF SIDEWALK TRAFFIC. IF
 THIS IS DOMESTIC BACKFLOW ASSEMBLY SHOULD BE LABELED
 RPPA INSTEAD AND NONE OF THOSE SHOULD BE INSIDE
 BUILDINGS. ALSO THIS WATER SERVICE IS AT AN UNSAFE AND
 INCONVENIENT LOCATION FOR MAINTENANCE BEING AT THE
 ENTRANCE FOR GARAGE -> SERVICE LINE SHOULD BE RELOCATED
 AWAY FROM THERE.
  
 -WATER MAIN MATERIAL SUCH AS D.I.P. IS NOT WRITTEN ON
 THE LABEL.
  
 -WATER MAIN CONFIGURATION ON BANYAN IS NOT SIMILAR TO
 OUR GIS -> NOT SURE WHICH ONE IS WRONG.
  
 -FOR THE SOUTHERN FIRELINE OFF BANYAN, CANNOT TELL IF
 IT IS INSIDE A BUILDING OR OUTSIDE. WOULD LIKE POINT OF
 SERVICE VALVE ADDED JUST INSIDE UE TO BETTER ESTABLISH
 POS AND REDUCE VALVE OPERATION ON STREET FOR SAFETY.
  
 -CANNOT FIND DOMESTIC METER ON PLAN. IT SHOULD BE AWAY
 FROM VEHICLE TRAFFIC AND OUT OF SIDEWALK IN SMALL UE
 OUTSIDE OF BUILDING AND BE ABOVE-GROUND IF 3? OR
 LARGER.
  
 -THERE IS A LABEL FOR PROPOSED FIRELINE ON THE WEST
 SIDE, BUT IT DOES NOT POINT TO ANYTHING.
  
 -SHEET DOES NOT HAVE DEMAND CHART SHOWING HOW MUCH
 WATER PROPERTY WILL USE.
  
 -CITY IS DOING A STREETSCAPE PROJECT ON BANYAN AND PLAN
 IS AT 90%. SHOULD CHECK WITH STREETSCAPE PROJECT TO SEE
 HOW BANYAN WILL BE DIFFERENT AND IF ANY COLLABORATION
 CAN TAKE PLACE.
  
 -FOR DOMESTIC WATER SERVICES ? UTILITIES RECOMMENDS
 PARALLEL ASSEMBLIES SO CUSTOMERS WILL NOT BE WITHOUT
 WATER DURING BACKFLOW ASSEMBLY MAINTENANCE.
  
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO, PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401 (MAILING ADDRESS: P.O. BOX
 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1098
 FAX: (561) 494-1116 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  
  Print


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved