| 2019-09-10 21:30:37 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. |
| | |
| | 2. LOCATION OF ACCESSIBLE PARKING SPACES WITHIN THE |
| | PARKING GARAGE. SHEET Z1 SHOWS THE 1ST AND 2ND FLOOR |
| | ACCESSIBLE PARKING SPACES LOCATED SUCH THAT THEY ARE |
| | NOT THE CLOSEST PARKING SPACES TO THE RETAIL UNIT OR |
| | THE ELEVATORS. ONE OF THE ACCESSSIBLE PARKING SPACES |
| | SHOULD BE THE CLOSEST PARKING SPACE TO ONE OF THE |
| | RETAIL ENTRY DOORS, AND THE REMAINING ACCESSIBLE |
| | PARKING SPACES ON THE 1ST AND 2ND FLOORS SHOULD BE THE |
| | CLOSEST PARKING SPACES TO THE ELEVATORS. PER SECTION |
| | 208.3 OF FLORIDA ACCESSIBILITY CODE, ACCESSIBLE PARKING |
| | SPACES ARE TO BE LOCATED ON THE SHORTEST POSSIBLE ROUTE |
| | OF TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE |
| | ENTRANCE. THE DESIGN OF ACCESSIBLE PARKING SPACES SHALL |
| | COMPLY WITH SECTION 502 OF FLORIDA ACCESSIBILITY CODE. |
| | |
| | 3. VAN ACCESSIBLE PARKING SPACES. NONE OF THE |
| | ACCESSIBLE PARKING SPACES HAVE BEEN DESIGNATED AS VAN |
| | ACCESSIBLE. TWO OF THEM SHOULD BE SO DESIGNATED. PER |
| | SECTION 208.2.4 OF FLORIDA ACCESSIBILITY CODE, ONE IN |
| | EVERY SIX REQUIRED ACCESSIBLE SPACES (AT LEAST ONE) IN |
| | A PARKING STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND |
| | DESIGNED IN ACCORDANCE WITH SECTION OF 502 OF FLORIDA |
| | ACCESSIBILITY CODE (VERTICAL CLEARANCE NOT LESS THAN 98 |
| | INCHES AT SPACE AND VEHICULAR ACCESS ROUTE) |
| | |
| | 4. ACCESSIBLE PARKING SPACE AISLE. WHEN ADDRESSING |
| | COMMENT # 2 ABOVE, PLEASE MAINTAIN THE CONDITIONS SUCH |
| | THAT ACCESSIBLE PARKING SPACE ACCESS AISLES ARE LOCATED |
| | SO THAT THE USER IS NOT COMPELLED TO WALK OR WHEEL |
| | BEHIND ANOTHER PARKED VEHICLE OR IN THE TRAVEL LANE. |
| | THE ACCESS AISLES SHALL ALSO COMPLY WITH THE OTHER |
| | PROVISIONS OF SECTION OF 502.3 OF FLORIDA ACCESSIBILITY |
| | CODE. |
| | |
| | 5. ACCESSIBLE PARKING SPACE FOR THE EXISTING |
| | BANK/OFFICE BUILDING. SITE PLAN, SHEET SP-1 SHOWS 9 |
| | EXISTING PARKING SPACES REMAINING. AN ACCESSIBLE |
| | PARKING SPACE IS REQUIRED. IF THE ACCESSIBLE SURFACE |
| | PARKING SPACE IS INTENDED TO SERVE THAT PURPOSE, PLEASE |
| | RELOCATE IT SUCH THAT IT IS THE CLOSEST PARKING SPACE |
| | TO THE BANK/OFFICE BUILDING ENTRANCE AND SUCH THAT THE |
| | USER IS NOT COMPELLED TO WALK OR WHEEL BEHIND ANOTHER |
| | PARKED VEHICLE OR IN THE TRAVEL LANE. PER SECTION 208.3 |
| | OF FLORIDA ACCESSIBILITY CODE, ACCESSIBLE PARKING |
| | SPACES ARE TO BE LOCATED ON THE SHORTEST POSSIBLE ROUTE |
| | OF TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE |
| | ENTRANCE. THE DESIGN OF ACCESSIBLE PARKING SPACES SHALL |
| | COMPLY WITH SECTION 502 OF FLORIDA ACCESSIBILITY CODE. |
| | |
| | 6. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, |
| | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR |
| | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, |
| | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE |
| | FLORIDA BUILDING CODE. |
| | |
| | 7. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND |
| | OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT, |
| | COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF |
| | OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF |
| | CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE |
| | VERIFIED. |
| | |
| | 8. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES |
| | NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO |
| | MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL |
| | BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE |
| | EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED |
| | TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR |
| | OTHER APPROVED METHODS. |
| | |
| | 9. GREASE INTERCEPTOR. IF THE RETAIL SPACE MIGHT |
| | INCLUDE A RESTAURANT, A GREASE INTERCEPTOR WILL BE |
| | REQUIRED. PLEASE CONTACT JEFFREY ODOMS, UTILITIES O&M |
| | SUPERINTENDENT, PUBLIC UTILITIES DEPARTMENT, FATS OILS |
| | AND GREASE DIVISION, AT (561) 822-2172, OR BY EMAIL: |
| | [email protected] |
| | |
| | 10. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS |
| | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE |
| | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED |
| | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, |
| | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND |
| | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, |
| | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. |
| | |
| | 11. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND |
| | CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF |
| | CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL |
| | NEIGHBORING PROPERTIES. |
| | |
| | 12. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER |
| | AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY, |
| | INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE |
| | CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF |
| | NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION |
| | THAT MAY AFFECT THE USE OF THEIR PROPERTY. |
| | |
| | 13. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT |
| | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL |
| | HAVE A SEPARATE ADDRESS. FOR STREET ADDRESSING, CONTACT |
| | MICHAEL ORIO, GIS SUPPORT SPECIALIST, AT (561) 494 |
| | 1080, OR BY EMAIL: [email protected] |
| | |
| | 14. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT |
| | TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE |
| | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP |
| | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC |
| | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: |
| | [email protected] |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |