2019-10-01 15:28:42THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 10/8/2019 REVIEW SUBMITTAL PACKAGE:
  
 1. PROPOSED DOGHOUSE DRAINAGE STRUCTURE (A-10) WILL BE
 LOCATED OVER EXISTING EXFILTRATION TRENCH. THE
 EXFILTRATION TRENCH WILL NEED TO BE MODIFIED BY
 REPLACING THE SLOTTED PIPE WITH SOLID PIPE CONNECTED TO
 THE DOG HOUSE STRUCTURE AND REPAIRING THE FABRIC LINED
 ROCK TRENCH. THE EQUIVALENT STORAGE IN THE CONVERTED
 EXFILTRATION TRENCH WILL NEED TO BE REPLACED ONSITE.
  
 2. CONSIDER PROVIDING 2 FEET OF PERVIOUS OVERHANG FOR
 THE SIX PARKING SPACES ALONG PROPERTY LINE L11 AS WELL
 AS FOR THE TWO PARKING SPACES ON THE OTHER SIDE OF THE
 SHARED DRIVE AISLE (WEST OF THE MEDICAL BUILDING).
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER