2019-10-08 17:10:40THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 SEPTEMBER 5, 2019 REVIEW SET OF PLANS:
  
 1. SHOW AND LABEL THE PERIMETER BERM AND PROVIDE A
 DETAIL/CROSS SECTION OF THE BERM.
  
 2. ALL DRAINAGE STRUCTURES CONNECTED TO EXFILTRATION
 TRENCHES SHALL HAVE POLLUTANT RETARDANT BAFFLES OVER
 THE EXFILTRATION PIPE (WHETHER "UPSTREAM" OR
 "DOWNSTREAM" OF THE EXFILTRATION TRENCH.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER