2020-02-28 17:22:41THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 FEBRUARY 13, 2020 REVIEW SUBMITTAL PACKAGE:
  
 1. REPLACE CONCRETE INLET TOP OF CATCH BASIN INLET ON
 THE NORTH SIDE OF TRINITY PL. WEST OF S. OLIVE AVE.
  
 2. ELIMINATE THE BLEEDER IN THE STORMWATER CONTROL
 STRUCTURE.
  
 3. THE HYDRAULIC GRADE LINE OF THE S. OLIVE AVE
 DRAINAGE SYSTEM SHOULD BE CONSIDERED IN THE SETTING OF
 THE WEIR ELEVATION FOR THE CONTROL STRUCTURE. IF THE
 WEIR IS SET TOO LOW, THERE MAY BE BACKFLOW INTO THE
 ONSITE DRAINAGE SYSTEM FROM THE ROADWAY DRAINAGE
 SYSTEM.
  
 4. EXFILTRATION TRENCH IS PROPOSED WITHIN THE BUILDING.
 THE VERTICAL CLEARANCE SHOULD BE DESIGNED FOR
 MAINTENANCE VEHICLES (E.G. VACUUM TRUCKS) ACCESS TO THE
 MANHOLES AND FOR CONSTRUCTION EQUIPMENT TO REPLACE THE
 EXFILTRATION TRENCH WHEN IT IS NO LONGER FUNCTIONING AS
 DESIGNED.
  
 5. WHY THE BREAK IN THE EXFILTRATION TRENCH ABOUT 65
 FEET NORTH OF THE SOUTH TRENCH DRAIN?
  
 6. CONSIDER MOVING THE NORTH TRENCH DRAIN ACROSS THE
 DRIVEWAY FURTHER SOUTH, AT A HIGHER RIM ELEVATION. THIS
 TRENCH MAY BECOME A BUBBLE UP STRUCTURE AND RELEASE
 WATER TOWARD TANGLEWOOD COURT WHEN ALL OFFSITE
 DISCHARGE SHOULD BE THROUGH THE CONTROL STRUCTURE.
  
 7. CONFIRM DRIVEWAY APRONS IN THE RIGHT OF WAY MEET
 CITY STANDARDS.
  
 8. LIST THE SEASONAL HIGH GROUNDWATER TABLE ELEVATION
 ON THE EXFILTRATION TRENCH DETAIL ST-8.
  
 9. LIST THE VERTICAL DATUM AND CONVERSION EQUATION TO
 NGVD1929 ON SHEET C4.02 AND ALL SHEETS WITH ELEVATION
 INFORMATION.
  
 10. LABEL THE STREETS ON THE EROSION AND SEDIMENTATION
 CONTROL PLAN SHEET.
  
 11. PROVIDE INLET PROTECTION DETAIL FOR AN INLET
 WITHOUT A HOOD OPENING. THERE ARE VALLEY GUTTER INLETS
 AND DITCH BOTTOM STYLE INLETS WITHIN THE RIGHT-OF-WAY.
  
 12. CAN CONSTRUCTION TRAFFIC ACCESS BE LIMITED TO THE
 SIDE STREETS AND NOT FROM S. OLIVE AVE.?
  