| 2019-11-27 10:27:32 | PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND |
| | STORMWATER INFRASTRUCTURE ALONG SEGMENTS WHERE YOU ARE |
| | CONNECTING. (PPRC REQUIREMENT). |
| | 8 INCH CONNECTION TO EXISTING CITY SANITARY SEWER SHALL |
| | BE MADE VIA A NEW DOGHOUSE STYLE MANHOLE. |
| | FOR THE ENGINEERING SUBMITTAL, CITY ENGINEERING |
| | SERVICES SUGGESTS ADDING IRRIGATION METER (WATER ONLY) |
| | TO ENGINEERING PLANS. |
| | |
| | |
| | THE FOLLOWING COMMENTS WERE UPLOADED ON 12/3/19 FOR |
| | MARK HURLEY, FIELD CUSTOMER SERVICE SUPERVISOR, CITY OF |
| | WPB PUBLIC UTILITIES. CONTACT [email protected], OR |
| | 561-822-2262. |
| | |
| | -U.E. IS CUTTING OFF SOME OF THE DOMESTIC WATER SERVICE |
| | PIPING. SHOULD BE EXTENDED EAST TO INCLUDE THE N-S |
| | PIPING. THAT N-S PIPING SHOULD ALSO HAVING LABEL WITH |
| | PIPE SIZE AND TYPE. |
| | -THE PREFERRED LARGE METER INSTALLATION IS THE |
| | ABOVE-GROUND VARIANT IN CONJUNCTION WITH WS-8 FOR |
| | INCREASED SAFETY, COST REDUCTION, AND EASE OF |
| | MAINTENANCE. SHOULD BE CHANGED TO ABOVE-GROUND INSTALL |
| | INSTEAD OF VAULT. THIS WOULD LIKELY ALSO ALLOW |
| | ELIMINATION OF 45?S BETWEEN METER AND BACKFLOW ASSEMBLY |
| | IF BYPASS IS PUT ON SOUTHERN SIDE AND METER ON NORTHERN |
| | SIDE. |
| | -THE PICTURE SHOWS PARALLEL DOMESTIC BACKFLOW |
| | ASSEMBLIES, WHICH IS GOOD. IF THAT IS AS INTENDED, |
| | SHOULD UPDATE LABEL TO MENTION PARALLEL ASSEMBLIES. |
| | -NOT SURE IF THE CIRCLE ICON ADJACENT EAST SIDE OF |
| | WATER METER IS A TREE. IF SO, IT IS TOO CLOSE TO THE |
| | PIPING. TREE SHOULD BE RELOCATED EAST APPROXIMATELY 5 |
| | FEET AND N-S ROOT BARRIER PLACED IN BETWEEN TREE AND |
| | PIPING. |
| | -IT LOOKS LIKE THE WATER SERVICES ARE CROSSING AND |
| | MULTIPLE FPL UTILITIES. PLAN SHOULD HAVE NOTATION ON |
| | HOW THIS CONFLICT IS RESOLVED. FOR EXAMPLE IS THE FPL |
| | BEING RELOCATED, OR DO THEY CROSS UNDER/OVER EACH |
| | OTHER. |
| | -THE WATER UTILITIES AND UE LOOK TO BE IN A 12? E-W |
| | PEDESTRIAN ACCESS EASEMENT. I AM NOT KNOWLEDGEABLE ON |
| | PEDESTRIAN EASEMENTS. PROJECT TEAM SHOULD VERIFY THAT |
| | IT IS ALRIGHT AND NOT PROBLEMATIC. |
| | -PAVEMENT RESTORATION JUST SHOWED HALF THE STREET, BUT |
| | EXISTING STREET LOOKS MORE LIKE A SINGLE LANE. PROJECT |
| | TEAM NEEDS TO VERIFY IF ALLOWED TO RESTORE LIKE THAT OR |
| | MUST RESURFACE ENTIRE WIDTH OF ROAD. |
| | -THERE IS AN EXISTING SMALL METERED WATER SERVICE ON |
| | THE EAST SIDE OF PROPERTY NEAR THE CENTER ON OLIVE. |
| | SHOULD BE DRAWN AND LABELED ON PLAN ALONG WITH WHAT |
| | WILL BE HAPPENING TO IT (REMOVED/CUT-BACK, CONTINUE |
| | USING FOR IRRIGATION, ETC?). CURRENTLY SHOW IT AS AN |
| | ACTIVE IRRIGATION WATER SERVICE FOR THE PROPERTY. |
| | -PROPOSED SS CROSSES WATER MAIN WHICH IS CONFLICT, BUT |
| | PLAN NOT SAY HOW CONFLICT IS RESOLVED. SHOULD BE |
| | LABELED WITH HOW CONFLICT IS RESOLVED. PREFERABLY WATER |
| | MAIN FEW FEET ABOVE SS. |
| | -FIRE HYDRANT AT NE CORNER OF PROPERTY NOT SHOWING UE |
| | AROUND IT -> LOOKS LIKE IT ON THE PRIVATE PROPERTY. |
| | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR |
| | CONCERNS, THANKS. |
| | |