| 2019-08-14 12:23:26 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. |
| | |
| | 2. NUMBER OF ACCESSIBLE PARKING SPACES. THE PARKING |
| | DATA TABLE ON SITE PLAN SHEET C3.00 STATES THAT 6 |
| | ACCESSIBLE PARKING SPACES WILL BE PROVIDED, BUT THE |
| | SUBMITTED LEVEL 1, LEVEL 2, AND LEVEL 3 PARKING PLANS |
| | ONLY SHOW A TOTAL OF 2 ACCESSIBLE PARKING SPACES. THE |
| | MINIMUM NUMBER OF ACCESSIBLE PARKING SPACES PROVIDED |
| | SHALL BE IN ACCORDANCE WITH SECTION 208.2 OF FLORIDA |
| | ACCESSIBILITY CODE. |
| | |
| | 3. LOCATION OF ACCESSIBLE PARKING SPACES. WHEN COMMENT |
| | NO. 2 IS ADDRESSED, PLEASE NOTE THAT, PER SECTION 208.3 |
| | OF FLORIDA ACCESSIBILITY CODE, ACCESSIBLE PARKING |
| | SPACES ARE TO BE LOCATED ON THE SHORTEST POSSIBLE ROUTE |
| | OF TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE |
| | ENTRANCE. THE DESIGN OF ACCESSIBLE PARKING SPACES SHALL |
| | COMPLY WITH SECTION 502 OF FLORIDA ACCESSIBILITY CODE. |
| | |
| | 4. VAN ACCESSIBLE PARKING SPACES. NO VAN ACCESSIBE |
| | PARKING SPACES HAVE BEEN SHOWN ON THE SUBMITTED PLANS. |
| | AT LEAST ONE OF THE PROPOSED ACCESSIBLE 6 ACCESSIBLE |
| | PARKING SPACES SHALL BE VAN ACCESSSIBLE. PER SECTION |
| | 208.2.4 OF FLORIDA ACCESSIBILITY CODE, ONE IN EVERY SIX |
| | REQUIRED ACCESSIBLE SPACES (AT LEAST ONE) IN A PARKING |
| | STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND DESIGNED IN |
| | ACCORDANCE WITH SECTION OF 502 OF FLORIDA ACCESSIBILITY |
| | CODE (VERTICAL CLEARANCE NOT LESS THAN 98 INCHES AT |
| | SPACE AND VEHICULAR ACCESS ROUTE). |
| | |
| | 5. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, |
| | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR |
| | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, |
| | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE |
| | FLORIDA BUILDING CODE. |
| | |
| | 6. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND |
| | OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT, |
| | COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF |
| | OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF |
| | CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE |
| | VERIFIED. PLEASE LOOK CLOSELY AT THE AREA OF GLAZING |
| | (UNPROTECTED OPENINGS) FOR THE MICRO-UNITS ON THE WEST |
| | SIDE OF THE BUILDING. |
| | |
| | 7. EXIT ACCESS VIA DEAD END CORRIDORS. THE SUBMITTED |
| | SCHEMATIC FLOOR PLANS FOR LEVELS 4 THROUGH LEVEL 8 DO |
| | NOT SHOW ANY DIMENSIONS, BUT THEY SHOW A DEAD END |
| | CORRIDOR AS THE ONLY ACCESS TO THE STAIR WHEN EXITTING |
| | THE AMENITIES AND THE MICRO-UNITS AT THE SOUTH END OF |
| | THE BUILDING. PER SECTION 1020.4 AND TABLE 1006.2.1 OF |
| | FLORIDA ACCESSIBILITY CODE, BUILDING, DEAD END |
| | CORRIDORS SHALL NOT EXCEED 50 FEET, AND COMMON PATH OF |
| | TRAVEL SHALL NOT EXCEED 125 FEET. ALSO, THE LEVEL 8 |
| | INDOOR AMENITY AND OUTDOOR AMENITY SPACES ARE ASSUMED |
| | TO BE ASSEMBLY OCCUPANCY WITH AN OCCUPANCY RATE OF 7 |
| | SQUARE FEET PER PERSON OR 15 SQUARE FEET PER PERSON SO |
| | THE NUMBER OF OCCUPANTS WILL BE GREATER SO EGRESS VIA A |
| | SINGE DEAD END CORRIDOR MAY BE PROBLEMATIC. |
| | |
| | 8. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES |
| | NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO |
| | MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL |
| | BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE |
| | EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED |
| | TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR |
| | OTHER APPROVED METHODS. |
| | |
| | 9. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS |
| | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE |
| | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED |
| | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, |
| | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND |
| | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, |
| | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. |
| | |
| | 10. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND |
| | CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF |
| | CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL |
| | NEIGHBORING PROPERTIES. |
| | |
| | 11. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER |
| | AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY, |
| | INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE |
| | CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF |
| | NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION |
| | THAT MAY AFFECT THE USE OF THEIR PROPERTY. |
| | |
| | 12. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT |
| | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL |
| | HAVE A SEPARATE ADDRESS. FOR STREET ADDRESSING, CONTACT |
| | MICHAEL ORIO, GIS SUPPORT SPECIALIST, AT (561) 494 |
| | 1080, OR BY EMAIL: [email protected] |
| | |
| | 13. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT |
| | TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE |
| | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP |
| | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC |
| | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: |
| | [email protected] |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |