| 2019-08-14 00:05:50 | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL |
| | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION |
| | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE |
| | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT |
| | APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT |
| | APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR |
| | MS,-PERMITS-APPLICATIONS |
| | |
| | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE |
| | PLAN APPROVAL: |
| | |
| | 1. MOVE THE DRAINAGE CONTROL STRUCTURE AND THE PIPE TO |
| | THE EAST OUT OF THE RIGHT-OF-WAY. AN ADDITIONAL |
| | DRAINAGE STRUCTURE MAY BE NEEDED NORTH OF THE PROPOSED |
| | CATCH BASIN INLET IN THE TRINITY PLACE R/W. |
| | |
| | 2. SHOW UTILITIES ON THE LANDSCAPE PLANS. |
| | |
| | 3. CONSIDER A STORMWATER MANAGEMENT SYSTEM DIFFERENT |
| | FROM EXFILTRATION TRENCHES. THE EFFECTIVE LIFE OF |
| | EXFILTRATION TRENCHES IS 5 ? 10 YEARS OR LESS BEFORE |
| | THEY WILL NEED TO BE REPLACED. DIGGING UP AND REPLACING |
| | THE TRENCHES WILL HAVE AN IMPACT ON THE INTERIOR |
| | TRAFFIC CIRCULATION. |
| | |
| | 4. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD |
| | CRITERIA FOR STORMWATER TREATMENT AND PEAK FLOW |
| | ATTENUATION FOR PRE- VS POST-DEVELOPMENT DISCHARGE. |
| | |
| | 5. THE DRAINAGE SYSTEM IN OLIVE AVE INCLUDES CONTROL |
| | STRUCTURES WHICH AFFECT THE HYDRAULIC GRADE LINE. THE |
| | HGL MAY BE HIGHER THAN THE WEIR ELEVATION IN THE |
| | PROPOSED CONTROL STRUCTURE. |
| | |
| | 6. PROVIDE CCTV OF THE EXISTING DRAINAGE SYSTEMS |
| | SURROUNDING THE PROJECT SITE. |
| | |
| | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO |
| | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING |
| | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. |
| | |
| | 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY |
| | BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT. |
| | THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS |
| | CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE |
| | ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS |
| | |
| | 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED |
| | WITH THE ENGINEERING PERMIT APPLICATION. |
| | |
| | 3. PROVIDE A COPY OF THE SFWMD ERP PERMIT PRIOR TO |
| | STARTING CONSTRUCTION. |
| | |
| | |