| 2019-07-31 13:22:49 | THE CITY OF WEST PALM BEACH HAS A NUMBER OF REGULATIONS |
| | AND PERMIT REQUIREMENTS WHICH DIRECTLY AFFECT THE |
| | DEVELOPMENT AND INSTALLATION OF WATER AND WASTEWATER |
| | UTILITIES WITHIN THE CITY. PLEASE SEE DEVELOPMENT |
| | PERMIT SUBMITTAL REQUIREMENTS AT THE LINK BELOW: |
| | HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WPB_W |
| | EBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FULL-P |
| | ACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97B19 |
| | 60045731D3658206F27451722716EF |
| | THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE |
| | FOUND HERE: |
| | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR |
| | MS,-PERMITS-APPLICATIONS |
| | |
| | CODE OF ORDINANCES, CITY OF WEST PALM BEACH, FLORIDA, |
| | CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED SEPT. 22, |
| | 2008. (SUPPLEMENT NO. 18) |
| | CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL, SEC. 90-7. |
| | POLICY REGARDING EXTENSION OF WATER OR SEWER SERVICE |
| | FACILITIES OF THE CITY. |
| | THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE |
| | CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY |
| | BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS, |
| | BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION. |
| | PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER ALONG |
| | ENTIRE PROJECT FRONTAGE. |
| | PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY OF |
| | WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC RIGHT |
| | OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF YOUR |
| | PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE |
| | MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL |
| | IN THE WPB ENGINEERING SERVICES DEPARTMENT AT |
| | [email protected] OR 561-494-1079 FOR FURTHER |
| | ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION |
| | ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD |
| | SURVEY, POT-HOLING, SOFT DIGS ETC. |
| | AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH |
| | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, |
| | STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR |
| | MORE INFORMATION, REFER TO THE LINK BELOW: |
| | HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI |
| | CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL |
| | PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS OF |
| | ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES, |
| | INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND |
| | SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES, |
| | METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE |
| | SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING |
| | GRADES, PIPES SIZES, MATERIALS, ELEVATIONS, |
| | ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL |
| | INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER |
| | LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE |
| | PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN |
| | VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS. |
| | ADDITIONALLY, PLAN VIEW SHALL SHOW ALL EXISTING AND |
| | PROPOSED UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER |
| | OPTIC, ELECTRIC, GAS, AND CABLEVISION & |
| | TELECOMMUNICATION FACILITIES LOCATED ON THE |
| | RIGHT-OF-WAY. PROVIDE PROFILE AND CLEARANCES AT ALL |
| | UTILITY CROSSINGS. |
| | CUT AND CAP UTILITIES NOT IN USE, AND REMOVE ANY |
| | ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY |
| | RIGHT OF WAY. |
| | PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE |
| | DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB |
| | DEVELOPMENT APPLICATION). |
| | PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND |
| | IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED |
| | AREAS. |
| | PROVIDE UTILITY EASEMENTS TO ALLOW ACCESS FOR CITY |
| | PERSONNEL TO PROPOSED UTILITIES INCLUDING WATER METERS. |
| | PROVIDE ADDRESS ON COVER SHEET. |
| | ON DEMOLITION PLAN, SHOW SILT FENCE, INLET PROTECTION, |
| | CONSTRUCTION ENTRANCE DETAILS, BEST MANAGEMENT |
| | PRACTICES, ETC. |
| | |
| | ADDITIONAL COMMENTS FROM MARK HURLEY, FIELD CUSTOMER |
| | SERVICE SUPERVISOR, PUBLIC UTILITIES, CITY OF WEST PALM |
| | BEACH, 561-822-2262, [email protected]: |
| | -THE 3 INCH DOMESTIC METER LOOKS LIKE IT MAY BE LOCATED |
| | INSIDE OF A BUILDING -> CANNOT BE LOCATED IN A |
| | BUILDING. THE DOMESTIC RP BACKFLOW CANNOT BE LOCATED |
| | INSIDE OF A BUILDING EITHER. ALSO LOOKS LIKE IT MIGHT |
| | BE IN A FOOT TRAFFIC PATH -> LIKE METER AWAY FROM FOOT |
| | TRAFFIC. CUSTOMER SHOULD INVESTIGATE ALTERNATE |
| | LOCATIONS SUCH AS EAST OR NORTH SIDE OF PROPERTY, AND |
| | CONSTRUCTING SMALL GRASS AREA FOR METER AND BACKFLOW. |
| | -UTILITIES DOES NOT WANT FIRE BACKFLOW INSIDE BUILDING |
| | UNLESS FIRE DEPT REQUIRES IT -> IF SO, THEN WOULD NEED |
| | BACKFLOW COVENANT COMPLETED AND SUBMITTED. DCDA TYPE |
| | ONLY APPROVED IF NO CHEMICALS ADDED IN DOWNSTREAM FIRE |
| | PIPING. |
| | -WATER SERVICES LOOK TO BE RUNNING ON PRIVATE PROPERTY. |
| | WOULD NEED UTILITY EASEMENTS CREATED FOR ALL THE |
| | DOMESTIC PORTION INCLUDING WATER METER. FOR THE FIRE |
| | PORTION, POINT OF SERVICE VALVE NOT MARKED (USUALLY IS |
| | JUST BEFORE PROPERTY LINE). CITY WATER SERVICE PIPING |
| | LENGTH IS NOT MINIMIZED -> EXTENDS FAR ON PROPERTY AND |
| | LOOKS LIKE IT MAY BE IN A ROAD -> WHICH WOULD SHUT DOWN |
| | THAT ENTRANCE/EXIT IN THE EVENT OF REPAIR WORK. |
| | -METER DOES NOT SAY IF IT IS ABOVE-GROUND OR |
| | UNDERGROUND -> FIELD CUSTOMER SERVICE PREFERS ABOVE |
| | GROUND FOR EMPLOYEE SAFETY AND COST REDUCTION WITH NO |
| | VAULT TO MAINTAIN. |
| | -CUSTOMER SHOULD CONSIDER PARALLEL BACKFLOW PREVENTER |
| | SETUP FOR DOMESTIC WATER SO THAT IF DOING MAINTENANCE |
| | ON BACKFLOW ALL THE DWELLINGS AND STORES DO NOT LOSE |
| | WATER. |
| | |
| | |
| | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR |
| | CONCERNS, THANKS. |
| | RICK ROSSANO |
| | PROJECT COORDINATOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET, 4TH FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| | MAIN PHONE: (561) 822-1200 |
| | DIRECT: (561) 494-1098 |
| | FAX: (561) 494-1116 |
| | MOBILE: (561) 246-9525 |
| | EMAIL: [email protected] |
| | WWW.WPB.ORG/ENGINEERING |
| | |
| | MANNY GONZALEZ |
| | SENIOR ENGINEERING PROJECT COORDINATOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET, 4TH FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| | MAIN PHONE: (561) 822-1200 |
| | DIRECT: (561) 494-1085 |
| | FAX: (561) 494-1116 |
| | MOBILE: (561) 644-7301 |
| | EMAIL: [email protected] |
| | WWW.WPB.ORG/ENGINEERING |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| |
Print |