2020-03-12 16:59:42THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 FEBRUARY 2020 DATED CIVIL PLANS:
  
 1. THE CITY'S VERTICAL DATUM IS NGVD1929. THE
 ENGINEERING PLANS ARE USING NAVD1988. LIST FHE VERTICAL
 DATUM BASIS AND CONVERSION EQUATION TO NGVD1929 ON
 EVERY SHEET WITH ELEVATION INFORMATION, INCLUDING THE
 SURVEY. [REPEAT COMMENT]
  
 2. ADJUST THE SILT FENCE TO INCLUDE THE NEW WATER MAIN
 CONSTRUCTION. [REPEAT COMMENT]
  
 3. STORMWATER WATER QUALITY TREATMENT AND PEAK FLOW
 ATTENUATION TO BE PROVIDED FOR THE NEW CONSTRUCTION.
 [REPEAT COMMENT]
  
 4. CONFLICTING CALLOUTS FOR STOIRM PIPE MATERIAL FOR
 CONSTRUCTING THE PIPE (RCP) AND CONNECTING TO CATCH
 BASINS (PVC).
  
 5. CLEANOUT CALLED OUT FOR ROOF DRAIN LATERAL
 CONNECTION TO RCP PIPE.
  
 6. ADD THE CITY'S PROJECT NUMBER TO THE COVER SHEET.
  
 7. SHOW LIMITS OF CONCRETE REPLACEMENT ALONG EAST SIDE
 OF TENNIS COURTS WHERE THE SANITARY SEWER IS BEING
 INSTALLED.
  
 8. IS SILT FENCE NEEDED ALONG THE EAST SIDE OF THE
 TENNIS COURTS?
  
 9. WHERE IS DRAINAGE STRUCTURE S-2?
  
 10. REPLACE THE WATER MAIN BETWEEN THE PROPOSED 6" X 6"
 X 2" TEE AND THE PROPOSED 45-DEGREE BEND.
  