| Plan Review Notes For Project Z19050027 |
| Project Number |
Z19050027 |
|
| Review Stop |
ENG - PPRC |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-03-13 08:16:00 | PASSED WITH PROVISOS: | | | | | | GENERAL: | | | RESPOND TO ALL COMMENTS IN WRITING. | | | SHOW VERTICAL DATUM AND DATUM CONVERSION INFORMATION | | | (NAVD 88 AND NGVD 29) ON ALL RELEVANT SHEETS. | | | | | | COVER SHEET : | | | ADD PROJECT ADDRESS. | | | | | | SHEET 9: | | | PROVIDE ENLARGED DETAIL ON PLANS OF PROPOSED LOCATION | | | OF WATER METER AND LEAD-FREE BACKFLOW PREVENTION. | | | PROVIDE CALCULATIONS ON PLANS OF EXISTING AND PROPOSED | | | DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM AND PEAK) | | | AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE PER FAC | | | 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER. | | | PROVIDE PROFILES AT ALL UTILITY CONFLICTS/CROSSINGS. | | | | | | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR | | | CONCERNS, THANKS. | | | | | | RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES | | | DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR WPB, FL 33401 (MAILING | | | ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1098 | | | FAX: (561) 494-1116 MOBILE: (561) 246-9525 | | | EMAIL: [email protected] WWW.WPB.ORG/ENGINEERING | | | |
| |