Plan Review Notes
Plan Review Notes For Project Z19050024
Project Number Z19050024
Review Stop ENG - PPRC
Sequence Number 5
Notes
Date Text
2020-09-23 16:42:52COMMENTS FROM MARK HURLEY, CITY OF WPB PUBLIC UTILITIES
 CUSTOMER SERVICE, [email protected] OR 561-822-2262:
  
 RESPONSE TO PRIOR COMMENT DOES NOT MAKE SENSE:
  
 2.) RECORDED BACKFLOW COVENANTS WILL BE REQUIRED FOR
 ANY FIRELINE BACKFLOW ASSEMBLIES LOCATED INSIDE
 BUILDINGS. MARK HURLEY CAN ASSIST WITH THAT PROCESS.
  
 RESPONSE: LIMITED IRRIGATION WATER WILL BE SOURCED FROM
 THE PROPOSED POTABLE METER. FINAL METER SIZING WILL BE
 COORDINATED AS PART OF THE CONSTRUCTION DRAWINGS /
 PERMIT SUBMITTALS.
 NEW COMMENTS:
  
 -PROPOSED FIRE HYDRANT MAY NOT BE LOCATED UNDER GUY
 WIRES. THIS LOOKS TO BE THE CASE AT BARCELONA. IF SO,
 PLEASE RELOCATE.
  
 -DURING ENGINEERING SUBMITTAL, VERIFY PROPOSED FIRE
 HYDRANT AT CORDOVA HAS NO CLEARANCE ISSUES WITH STREET
 SIGNS. IF CONFLICT EXISTS, LOCATION WILL NEED TO BE
 ADJUSTED.
  
  