| 2020-01-21 08:47:13 | 1.) THE MAXIMUM HEIGHT OF THE FLAMINGO BUILDING IS 75 |
| | FT. (NOT 71.8 FT.) AS NOTED IN THE ARCHITECTURAL PLANS. |
| | THE HEIGHT AND SETBACK CALCULATIONS AND TABLE |
| | INFORMATION SHOULD BE REVISED TO ADDRESS THE MAXIMUM |
| | HEIGHT. [NOTE: THIS COMMENT WAS MISSED BY STAFF IN THE |
| | LAST RESUBMITTAL] |
| | |
| | 2.) THERE IS A PROPOSED 8 FT. HIGH CONCRETE WALL ALONG |
| | THE EAST PROPERTY LINE ABUTTING 314 FLAMINGO DRIVE. THE |
| | EXISTING STRUCTURE AT 314 FLAMINGO DRIVE SEEMS TO HAVE |
| | A 0 FT. SETBACK FROM THE PROPERTY LINE (NEEDS TO BE |
| | VERIFIED). IF THIS IS THE CASE, THE LOCATION OF THE |
| | PROPOSED WALL WILL NEED TO BE RELOCATED SO AS NOT TO |
| | CONFLICT WITH THE EXISTING STRUCTURE. [NOTE: THIS |
| | COMMENT WAS MISSED BY STAFF IN THE LAST RESUBMITTAL] |
| | |
| | 3.) THE PROPOSED NUMBER OF STORIES SEEM TO BE 5 (NOT 4) |
| | SINCE USABLE SPACE (I.E. GYM) IS LOCATED ON THE 5TH |
| | FLOOR. INFORMATION PROVIDED IN THE PLANS SHOULD BE |
| | ADDRESSED ACCORDINGLY. [NOTE: THIS COMMENT WAS MISSED |
| | BY STAFF IN THE LAST RESUBMITTAL] |
| | |
| | 4.) CHECK THE PROPOSED PARKING COUNT. THE COUNT STILL |
| | SEEMS TO BE INCORRECT AND IT HAS AFFECTED THE |
| | CALCULATIONS FOR PARKING. ADDRESS FOR CONSISTENCY. |
| | |
| | 5.) THE BUILDING FOOTPRINT PROVIDED IN THE |
| | ARCHITECTURAL DRAWINGS SEEM TO BE INCONSISTENT. CLARIFY |
| | FOR CONSISTENCY. |
| | |
| | 6.) SOME SPACES WITHIN THE ARCHITECTURAL PLANS HAVE |
| | BEEN EXCLUDED FROM THE FAR CALCULATIONS WHICH STAFF |
| | BELIEVES SHOULD HAVE BEEN INCLUDED IN THE FAR |
| | CALCULATIONS. THE ARCHITECT MUST CLARIFY THESE SPACES |
| | AND ADJUST THE FAR CALCULATIONS IN ALL APPLICABLE PLANS |
| | ACCORDINGLY. |
| | |
| | 7.) DEMONSTRATE THAT THE BICYCLE STORAGE AREAS CAN |
| | ACCOMMODATE THE PROPOSED NUMBER OF BICYCLE PARKING |
| | SPACES. |
| | |
| | 8.) THE ARCHITECT WILL NEED TO MEET WITH STAFF TO |
| | CLARIFY OTHER MINOR INCONSISTENCIES WITH THE FAR |
| | CALCULATIONS AS DEPICTED IN THE ARCHITECTURAL FLOOR |
| | PLANS. |
| | |
| | 9.) IT IS ADVISED THAT THE APPLICANT MEET WITH STAFF TO |
| | DISCUSS THE INCONSISTENCIES AND CONCERNS WITH THE |
| | PROJECT. PLEASE CONTACT STAFF TO SET UP A MEETING. |
| | |
| | |
| | INSTRUCTIONS FOR RESUBMITTAL |
| | |
| | * PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN |
| | WRITTEN FORMAT. |
| | |
| | * CHANGES ON THE RESUBMITTED PLANS MAY RESULT IN |
| | ADDITIONAL COMMENTS. |
| | |
| | * INCLUDE THE REVISION DATE TO ANY REVISED SHEETS TO |
| | KEEP TRACK OF ALL CHANGES MADE TO THE PROJECT. |
| | |
| | * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF |
| | FIFTEEN (15) PAPER COPIES, ONE (1) REDUCED COPY IN 8.5 |
| | INCHES X 11 INCHES, AND ONE (1) SET IN 11 INCHES X 17 |
| | INCHES, AND AN ELECTRONIC COPY OF ALL PLANS. |
| | |
| | * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) |
| | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED |
| | COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE |
| | APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE |
| | WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($600.00). |
| | |