| 2020-08-13 11:05:24 | COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR, |
| | [email protected], 561-494-1098: |
| | |
| | FOR ENGINEERING SUBMITTAL: |
| | |
| | SHOW ADJACENT ADDRESSES ON FLAMINGO RD. WHERE UTILITIES |
| | ARE BEING REPLACED. |
| | ADD CITY OF WPB PAVEMENT RESTORATION NOTE. |
| | SHOW LENGTH OF PROPOSED UTILITIES IN ROW. |
| | SHOW PROFILE/CLEARANCES AT ALL UTILITY CROSSINGS. |
| | IDENTIFY ALL PROPOSED SANITARY TIE-INS. |
| | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR |
| | CONCERNS, THANKS. |
| | |
| | |
| | COMMENTS FROM MARK HURLEY, CITY OF WPB PUBLIC UTILITIES |
| | CUSTOMER SERVICE, [email protected] OR 561-822-2262: |
| | |
| | -RECORDED BACKFLOW COVENANTS WILL BE REQUIRED FOR ANY |
| | FIRELINE BACKFLOW ASSEMBLIES LOCATED INSIDE BUILDINGS. |
| | MARK HURLEY CAN ASSIST WITH THAT PROCESS ? |
| | [email protected] |
| | -RECOMMEND DRAINS BE INSTALLED IN FIRE ROOMS CONTAINING |
| | FIRELINE BACKFLOW ASSEMBLIES. |
| | -WILL IRRIGATION WATER BE USED FROM THE WATER SERVICES? |
| | IF SO, PLEASE ADD TO DEMAND CALCULATION AND VERIFY |
| | WATER SERVICES ARE SUFFICIENT. |
| | -ON FORMAL ENGINEERING SUBMITTAL LABEL THE POINT OF |
| | SERVICE GATE VALVES FOR EACH FIRELINE WATER SERVICE. |
| | -RELOCATE GATE VALVES THAT ARE LOCATED IN THE PATH OF |
| | PEDESTRIAN FOOT TRAFFIC AND DOORS. |
| | -ARE ANY FIRE HYDRANTS PROPOSED TO BE INSTALLED? |
| | -RECOMMEND DUAL/PARALLEL BACKFLOW ASSEMBLIES TO REDUCE |
| | OUTAGES DURING BACKFLOW MAINTENANCE. |
| | -THE FOOTPRINT OF THE WATER SERVICES, METERS, AND |
| | BACKFLOW ASSEMBLIES MAY GET MUCH LARGER IF THEY ARE |
| | SIZED 3? OR GREATER. IF 3 IN. OR LARGER, USE THE |
| | ABOVE-GROUND STANDARD DETAIL. |
| | -IF THE WATER MAIN ON DIXIE IS 12 IN., WPB UTILITIES |
| | ENGINEER MAY PROVIDE MORE REQUIREMENTS AND DIRECTION. |
| | -WILL THE BUILDINGS BETWEEN BARCELONA AND FLAMINGO BE |
| | FED BY ONE DOMESTIC WATER METER, OR ARE WATER SERVICES |
| | MISSING FROM PLAN? |
| | -EXISTING WATER SERVICE TO PROPERTY WILL NEED TO BE |
| | IDENTIFIED ON ENGINEERING SUBMITTAL AND LABELED WITH |
| | WHAT IS HAPPENING TO THEM. |
| | |
| |