2020-01-13 09:39:44THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 DECEMBER 31, 2019 SUBMITTAL PACKAGE:
  
 1. MINIMUM STORMWATER PIPE SIZE IN THE RIGHT OF WAY IS
 15" RCP. THE FLAMINGO DRIVE STORMWATER EXTENSION WILL
 NEED TO REPLACE THE EXISTING 12" PIPE ON THE WEST SIDE
 OF OLIVE AVE.
  
 2. THE STORMWATER SYSTEMN EXTENSION PROPOSED ON
 BARCELONA ROAD WILL AFFECT THE EXISTING LANDSCAPED
 BULBOUT ON THE STREET.
  
 3. THE DRAINAGE SYSTEM EXTENSIONS IN THE RIGHT OF WAY
 WILL NEED TO BE PROVIDED ON A SEPARATE SET OF PLANS AND
 APPROVED BY THE PUBLIC UTILITIES DEPARTMENT OR
 ENGINEERING SERVICES DEPARTMENT. BASE SHEETS SHALL
 INCLUDE TOPOGRAPHIC SURVEY INFORMATION.
  
 4. ONSITE STOMWATER RUNOFF TO BE CAPTURED AND ROUTED
 THROUGH THE ONSITE STORMWATER RMANAGEMENT SYSTEM. STAFF
 COULD NOT DETERMINE HOW THE RUNOFF FROM THE DRIVEWAYS
 WILL BE CAPTURED BEFORE LEAVING THE SITE.
  
 5. ROOF DOWNSPOUTS TO BE DIRECTED TO THE ONSITE
 STORMWATER MANAGEMENT SYSTEM.
  
 6. SIDEWALKS ACROSS THE DRIVEWAYS TO BE CONSTRUCTED OF
 CONCRETE.
  
 7. REVISE THE ADA MAT FOR THE CURB RAMP ON THE EAST
 SIDE OF THE MAIN DRIVEWAY TO FLAMINGO ROAD TO FOLLOW
 THE CURB LINE.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120