Plan Review Notes
Plan Review Notes For Project Z19050024
Project Number Z19050024
Review Stop STORM
Sequence Number 2
Notes
Date Text
2019-10-09 15:43:19THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 OCTOBER 9, 2019 REVIEW SUBMITTAL PACKAGE:
  
 1. IT APPEARS THE PROPOSED BUMPOUTS IN THE PARKING
 SPACES ON S. DIXIE HIGHWAY WILL BLOCK THE DRAINAGE FLOW
 IN THE GUTTER.
  
 2. STAFF CANNOT DISCERN HOW THE STORMWATER RUNOFF IS
 BEING CONVEYED TO THE PROPOSED CASCADE SEPARATORS FOR
 WATER QUALITY TREATMENT..
  
 3. SHOW WHERE THE ROOF DOWNSPOUTS WILL BE LOCATED AND
 HOW THAT FLOW WILL BE CONNECTED TO THE ONSITE
 STORMWATER MANAGEMENT SYSTEM.
  
 4. LABEL MINIMUM 6 FEET OF HORIZONTAL SEPARATION
 BETWEEN OUTSIDE WALLS OF WATER MAINS, STORMWATER MAINS
 AND SEWER MAINS.
  
 5. SHOW MILL AND RESURFACE LIMITS FOR THE TRENCH CUTS
 ON S. DIXIE HWY.
  
 6. PROVIDE CROSS SECTIONS FROM THE ROAD CENTERLINE TO
 FACE OF BUILDING OF EACH ON-STREET PARKING AREA TO SHOW
 PAVEMENT AND SIDEWALK WIDTHS/SLOPES. SHWO THE LOCATION
 OF THE RIGHT-OF-WAY LINE ON EACH CROSS SECTION.
  
 7. REVISED SURVEY NOT INCLUDED IN THE REVIEW PACKAGE.
  
 8. PROVIDE CORRESPONDENCE FROM FDOT THAT THEY HAVE NO
 OBJECTIONS TO THE STOMRWATER SYSTEM CONNECTING TO THE
 S. DIXIE HWY DRAINAGE SYSTEM.
  
 9. CURB RAMPS WILL HAVE TO BE RECONSTRUCTED TO CURRENT
 ADA REQUIREMENTS (INCLUDED THE TRUNCATED DOMES) IF THE
 ASPHALT ADJACENT TO THE CURB RAMP IS
 DISTURBED/MODIFIED. THIS WILL APPLY TO THE NE CORNER OF
 FLAMINGO DRIVE AND SE CORNER OF CORDOVA ROAD.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120