| 2019-06-11 21:45:15 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. |
| | |
| | 2. LOCATION OF ACCESSIBLE PARKING SPACES. GARAGE |
| | PARKING LEVEL PLANS A-107 AND A-108 SHOW REGULAR |
| | PARKING SPACES LOCATED CLOSER TO THE ELEVATORS THAN THE |
| | ACCESSIBLE PARKING SPACES IN THE FLAMING DRIVE PARKING |
| | GARAGE. PER SECTION 208.3 OF FLORIDA ACCESSIBILITY |
| | CODE, ACCESSIBLE PARKING SPACES ARE TO BE LOCATED ON |
| | THE SHORTEST POSSIBLE ROUTE OF TRAVEL FROM ADJACENT |
| | PARKING TO AN ACCESSIBLE ENTRANCE. THE DESIGN OF |
| | ACCESSIBLE PARKING SPACES SHALL COMPLY WITH SECTION 502 |
| | OF FLORIDA ACCESSIBILITY CODE |
| | |
| | 3. VAN ACCESSIBLE PARKING SPACES. PER SECTION 208.2.4 |
| | OF FLORIDA ACCESSIBILITY CODE, ONE IN EVERY SIX |
| | REQUIRED ACCESSIBLE SPACES (AT LEAST ONE) IN A PARKING |
| | STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND DESIGNED IN |
| | ACCORDANCE WITH SECTION OF 502 OF FLORIDA ACCESSIBILITY |
| | CODE (VERTICAL CLEARANCE NOT LESS THAN 98 INCHES AT |
| | SPACE AND VEHICULAR ACCESS ROUTE) |
| | |
| | 4. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, |
| | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR |
| | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, |
| | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE |
| | FLORIDA BUILDING CODE. |
| | |
| | 5. EGRESS FROM THEATER LOBBY. SECOND FLOOR PLAN A-10.2 |
| | SHOWS A LONG NARROW STAIR FLIGHT LOCATED BETWEEN CINEMA |
| | 5 AND CINEMA 6 BUT THE STAIR DOES NOT SEEM TO LINE UP |
| | WITH THE LOCATION AND CONFIGURATION OF THE STAIR SHOWN |
| | ON FIRST FLOOR PLAN A1.01 OR MEZZANINE LEVEL PLAN |
| | A-1.01A. |
| | |
| | 6. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES |
| | NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO |
| | MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL |
| | BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE |
| | EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED |
| | TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR |
| | OTHER APPROVED METHODS. |
| | |
| | 7. GREASE INTERCEPTOR. A GREASE INTERCEPTOR WILL BE |
| | REQUIRED. PLEASE CONTACT JEFFREY ODOMS, UTILITIES O&M |
| | SUPERINTENDENT, PUBLIC UTILITIES DEPARTMENT, FATS OILS |
| | AND GREASE DIVISION, AT (561) 822-2172, OR BY EMAIL: |
| | [email protected] |
| | |
| | 8. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS |
| | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE |
| | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED |
| | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, |
| | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND |
| | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, |
| | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. |
| | |
| | 9. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND |
| | CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF |
| | CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL |
| | NEIGHBORING PROPERTIES. |
| | |
| | 10. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER |
| | AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY, |
| | INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE |
| | CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF |
| | NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION |
| | THAT MAY AFFECT THE USE OF THEIR PROPERTY. |
| | |
| | 11. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT |
| | TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE |
| | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP |
| | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC |
| | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: |
| | [email protected] |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |