Plan Review Notes
Plan Review Notes For Project Z19050020
Project Number Z19050020
Review Stop ENG - PPRC
Sequence Number 2
Notes
Date Text
2019-08-29 12:50:06PASSED WITH PROVISOS:
  
 FOR ENGINEERING SUBMITTAL:
  
 PROVIDE CALCULATIONS ON PLANS FOR FIRE FLOW DEMANDS.
  
 PLEASE ADD NOTE FOR PAVEMENT RESTORATION (100?) ON
 UTILITY PLAN WHERE THE WATER TAP IS TO BE PERFORMED PER
 CITY OF WPB STANDARD DETAIL GC-9.
  
 PLEASE SHOW CONSTRUCTION OF DUMPSTER TO BE IN
 COMPLIANCE WITH CITY OF WPB STANDARD DETAIL GC-8.
  
 PLEASE SHOW OVERHEAD CLEARANCE DIMENSIONS WHERE
 PROPOSED DUMPSTER IS TO BE CONSTRUCTED.
  
 PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED
 UNDERGROUND FRANCHISED UTILITIES, INCLUDING FIBER
 OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES LOCATED IN THE
 RIGHT-OF-WAY. (FRANCHISED UTILITIES WERE NOT SHOWN ON
 RESUBMITTED PLANS.)
  
 PROVIDE CLEARANCES AT ALL UTILITY (SANITARY, WATER,
 STORMWATER) CROSSINGS.
  
 PROVIDE SEWER TIE-IN INVERT ELEVATION.
  
 SHOW DOWNSTREAM SEWER FROM CONNECTION ONTO DIXIE HWY.
  
 CUT AND CAP UTILITIES NOT IN USE, AND REMOVE ANY
 ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY
 RIGHT OF WAY.
  
 CALL OUT SIZE OF EXISTING WATER SERVICE TO BE CUT OFF
 AT 12 IN. WATER MAIN.
  
 PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED
 AREAS. (NOT SHOWN ON SITE PLAN SUBMITTED WITH
 RESPONSE.)
  
 RELOCATE WATER METER BOX OUT OF SIDEWALK, ON PROPERTY,
 IN A DEDICATED EASEMENT. BACKFLOW TO BE AS CLOSE TO
 METER AS POSSIBLE (OUTSIDE OF EASEMENT).
  
 REMOVE BACKFLOW SHOWN NORTH OF PROPOSED 90 DEGREE BEND
 IN WATER SERVICE.
  
 PLEASE CALL OUT NUMBER OF FEET OF PIPE RESTRAINT PER
 CITY OF WPB STANDARD DETAIL P-3.
  
 PLEASE CROSS-REFERENCE ALL CROSS SECTIONS WITH THEIR
 CORRESPONDING SHEETS.
  
 ADD CITY OF WPB STANDARD DETAILS P-3, P-6, WS-6, WS-10.
  
 CLEARLY SHOW RIGHT OF WAY AND PROPERTY LINES.
  
 PLEASE NOTE THAT VIDEO WILL NEED TO BE PROVIDED BEFORE
 AND AFTER CONSTRUCTION BUT IS NOT REQUIRED AT THIS
 TIME.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 DIRECT: (561) 494-1098
 MOBILE: (561) 246-9525
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  
  Print


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved