Plan Review Notes
Plan Review Notes For Project Z19050019
Project Number Z19050019
Review Stop STORM
Sequence Number 2
Notes
Date Text
2019-08-19 11:04:25THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE JULY
 30, 2019 SUBMITTAL PACKAGE.
  
 1. IT APPEARS ONLY ROOF DRAINS AND CONDENSATE LINES ARE
 CONNECTED TO THE EXFILTRATION SYSTEMS. SINCE ALL ROOF
 DRAINAGE IS TO BE CAPTURED AND RETAINED ONSITE, WEIRS
 AND OUTFALL PIPES WILL NOT BE NECESSARY TO CONNECT TO
 THE OFFSITE DRAINAGE SYSTEMS. [REPEAT COMMENT]
  
 2. GRADING INFORMATION PROVIDED FOR THE DROPOFF AREA ON
 WEST STREET APPEARS TO SHOW A LOW SPOT ELEVATION OF
 20.13. IS THIS AREA DESIGNED TO HOLD WATER INSTEAD OF
 DRAINAGE TO AN INLET?
  
 3. PREVIOUS COMMENT REGARDING TREES PROPOSED OVER THE
 EXISTING DRAINAGE SYSTEM ON S. ROSEMARY AVE. WAS
 APPARENTLY ADDRESSED BY CROSS HATCHING THE AREA ON THE
 LANDSCAPE PLANS AND INDICATING THE AREA WAS APPROVED BY
 CITY COUNCIL (SIC) AS PART OF FACE OF THE CITY
 RESOLUTION.
  
 4. ON SHEET LH-03 ARE TWO SAND SET PAVER DETAILS.
 PLEASE INDICATE ON SHEET LH-01 WHERE EACH DETAIL
 APPLIES.
  
 5. INDICATE ON THE PGD PLAN HOW STORMWATER RUNOFF FROM
 THE PERIMETER SIDEWALK AREAS WILL BE CAPTURED ONSITE.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  