| 2019-06-07 07:20:10 | PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER ALONG |
| | ENTIRE PROJECT FRONTAGE. |
| | |
| | PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY OF |
| | WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC RIGHT |
| | OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF YOUR |
| | PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE |
| | MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL |
| | IN THE WPB ENGINEERING SERVICES DEPARTMENT AT |
| | [email protected] OR 561-494-1079 FOR FURTHER |
| | ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION |
| | ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD |
| | SURVEY, POT-HOLING, SOFT DIGS ETC. |
| | |
| | AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH |
| | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, |
| | STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR |
| | MORE INFORMATION, REFER TO THE LINK BELOW: |
| | HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI |
| | CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL |
| | |
| | PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS OF |
| | ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES, |
| | INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND |
| | SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES, |
| | METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE |
| | SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING |
| | GRADES, PIPES SIZES, MATERIALS, ELEVATIONS, |
| | ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL |
| | INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER |
| | LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE |
| | PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN |
| | VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS. |
| | ADDITIONALLY, PLAN VIEW SHALL SHOW ALL EXISTING AND |
| | PROPOSED UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER |
| | OPTIC, ELECTRIC, GAS, AND CABLEVISION & |
| | TELECOMMUNICATION FACILITIES LOCATED ON THE |
| | RIGHT-OF-WAY. PROVIDE PROFILE AND CLEARANCES AT ALL |
| | UTILITY CROSSINGS. |
| | |
| | CUT AND CAP UTILITIES NOT IN USE, AND REMOVE ANY |
| | ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY |
| | RIGHT OF WAY. |
| | |
| | PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE |
| | DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB |
| | DEVELOPMENT APPLICATION). |
| | |
| | PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND |
| | IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED |
| | AREAS. |
| | |
| | PROVIDE ONSITE CLEANOUTS AT PROPERTY LINE FOR PROPOSED |
| | SANITARY LATERALS. |
| | |
| | PROVIDE UTILITY EASEMENTS TO ALLOW ACCESS FOR CITY |
| | PERSONNEL TO PROPOSED UTILITIES INCLUDING WATER METERS. |
| | |
| | DELINEATE CITY OF WPB UTILITY EASEMENTS AND/OR RIGHTS |
| | OF WAY. PLEASE BOLD THE 25' ACCESS & UTILITY EASEMENT |
| | ON SHEET C6. |
| | |
| | PROVIDE ENLARGED DETAIL ON PLANS OF PROPOSED LOCATION |
| | OF WATER METER AND BACKFLOW PREVENTION. |
| | |
| | |
| | THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD |
| | CUSTOMER SERVICE SUPERVISOR, PUBLIC UTILITIES, CITY OF |
| | WEST PALM BEACH, 561-822-2262 |
| | |
| | SHEET P1.01: |
| | |
| | -BACKFLOW PREVENTERS ARE LABELED AS INDOORS. SHOULD NOT |
| | BE INDOORS, SHOULD BE OUTSIDE CLOSE TO WATER SERVICE AS |
| | POSSIBLE ON PRIVATE PROPERTY OUTSIDE OF ROW/UE. |
| | |
| | -ALL OF THE BACKFLOW PREVENTERS ARE MARKED AS DOUBLE |
| | CHECK. THEY SHOULD BE RPZ. |
| | |
| | -VERTICAL INSTALLATION MAY NOT BE USC APPROVED OR |
| | MANUFACTURER APPROVED FOR THE ASSEMBLY THEY ARE |
| | INSTALLING. WOULD EITHER NEED FIND APPROVED-ASSEMBLY OR |
| | CHANGE INSTALLATION TO HORIZONTAL. |
| | |
| | -DID NOT SEE FIRELINE DCDAS ON PLAN? NOT SURE IF THEY |
| | ARE SHOWN ON THEIR UTILITY PLAN INSTEAD? I THINK THERE |
| | ARE SOME EXISTING ONES ON SITE.. THEY SHOULD PUT ON |
| | PLANS WITH THE EXISTING WATER SERVICES AND SHOW |
| | CONNECTION/DESIGN/ETC. IF THEY FORGOT TO DRAW THE DCDA, |
| | THEN THEY SHOULD RE-DRAW & LABEL. THEY CANNOT USE THE |
| | DOMESTIC WATER SERVICES FOR FIRE WATER USES SUCH AS |
| | FIRE SPRINKLERS. |
| | |
| | -FIELD CUSTOMER SERVICE RECOMMENDS CUSTOMERS INSTALL |
| | PARALLEL BACKFLOW PREVENTERS SO CUSTOMERS STILL HAVE |
| | WATER DURING BACKFLOW MAINTENANCE OR PROBLEMS.PLEASE |
| | SEE SINGLE INSTALLATION HERE, DON'T KNOW IF THEY |
| | CONSIDERED DOING THAT. |
| | |
| | -CAN'T TELL IF METER BOXES/VAULTS ARE IN GRASS AND |
| | WHERE PROPERTY LINE AND UES ARE FROM DRAWING. PREFER |
| | BOXES IN GRASS AND OUT OF SIDEWALKS.SHOULD BE IN |
| | UE/ROW/PARKWAY. |
| | |
| | SHEET C6.00: |
| | |
| | -METER BOXES AND VAULTS APPEAR TO BE IN SIDEWALK. |
| | THAT'S A SAFETY HAZARD AND ALSO HAVE TO CLOSE SIDEWALK |
| | DURING METER MAINTENANCE. BOXES AND LIDS SHOULD BE |
| | LOCATED OUT OF SIDEWALKS. CUSTOMER NEEDS TO DEVELOP |
| | AREA PREFERABLY WITH GRASS BETWEEN SIDEWALKS AND |
| | BUILDING WHERE VAULTS AND METER BOXES CAN LIE AND WON'T |
| | BE WALKED ON IN REGULAR TRAFFIC PATHS. THEY CAN |
| | SET-BACK OR REDESIGN BUILDING FOOTPRINT IF NEEDED AND |
| | CREATE UTILITY EASEMENT. |
| | |
| | -ALL OF EXISTING UTILITIES NOT SHOWN. IN OUR BILLING |
| | SYSTEM I SEE EXISTING 3 IN. METER AND 8 IN. FIRELINE |
| | WITH DETECTOR METER. |
| | |
| | -8 IN. FIRELINE DCDA ARE PRETTY BIG. ON THE UTILITY |
| | DRAWING IT DOES NOT SHOW THE FOOTPRINT AND EXACT |
| | LOCATION OF PROP 8 IN. DCDA. CUSTOMER MAY HAVE |
| | DIFFICULTY FITTING THERE. THIS MAY REQUIRE SPECIAL |
| | PROTECTION IF LOCATED ADJACENT OUTSIDE WALL BY FIRE |
| | DEPARTMENT. |
| | |
| | -CUSTOMER PROPERTY LINE NOT SHOWING IN ALLEY -> NOT |
| | SURE IF PRIVATELY OWNED ROAD? -> UTILITY EASEMENT MAY |
| | NEED BE ASSIGNED TO ALL THE WATER UTILITY MAIN, |
| | SERVICE, AND METERS BOXES. |
| | |
| | -STANDARD DETAILS REFERENCES NOT SHOWN AND LABELED BY |
| | CITY WPB WSD# |
| | |
| | -VAULT IS FAR FROM EXISTING CONNECTION -> ADDITIONAL |
| | WATER SERVICE PIPING BEFORE VAULT SHOULD BE MINIMIZED. |
| | |
| | |
| | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR |
| | CONCERNS, THANKS. |
| | |
| | RICK ROSSANO |
| | PROJECT COORDINATOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET, 4TH FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| | MAIN PHONE: (561) 822-1200 |
| | DIRECT: (561) 494-1098 |
| | FAX: (561) 494-1116 |
| | MOBILE: (561) 246-9525 |
| | EMAIL: [email protected] |
| | WWW.WPB.ORG/ENGINEERING |
| | |
| | MANNY GONZALEZ |
| | SENIOR ENGINEERING PROJECT COORDINATOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET, 4TH FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| | MAIN PHONE: (561) 822-1200 |
| | DIRECT: (561) 494-1085 |
| | FAX: (561) 494-1116 |
| | MOBILE: (561) 644-7301 |
| | EMAIL: [email protected] |
| | WWW.WPB.ORG/ENGINEERING |
| | |
| | CENTRAL OPERATIONS CENTER (DISPATCH): |
| | 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC |
| | UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210 |
| | |
| | |
| |