Plan Review Notes
Plan Review Notes For Project Z19040051
Project Number Z19040051
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-05-22 10:40:32THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
  
 1) THERE IS NO INDICATION OF OCCUPANCY LOADS, TRAVEL
 PATHS, THAT SHOW COMPLIANCE WITH THE FLORIDA FIRE
 PREVENTION CODE.
  
 A LIFE SAFETY REVIEW IS REQUIRED TO SHOW OCCUPANCY
 LOADS, EXIT WIDTHS, TRAVEL DISTANCES, EXIT
 INDENTIFICATION/SIGNS, ETC.
  
  
  
 2) THERE ARE GATES INDICATED THAT APPEAR TO BE EXITS.
  
 HOW WILL THESE GATES OPERATE AND TYPE OF EXIT HARDWARE?
  
  
  
 3) THERE IS A SMALL ROOM/SPACE INDICATED/LABELED
 DIFFERENTLY(STORAGE/PRE-FUNCTION) ON TWO SPEARATE
 SHEETS.
  
 WHAT WILL THIS SMNALL ROOM/SPACE BE USED FOR?
  
  
  
 4) THERE APPEARS TO BE AN EXIT GATE ON THE WEST SIDE
 THAT CONVERGES ON THE EXIT WALKWAY OF THE CONVENTION
 CENTER THAT HAS MULTIPLE EXITS DOORS.
  
 PER # 1 ABOVE PLEASE INDICATE THAT THE COMBINED
 PROPOSED OCCUPANCY LOAD OF BOTH AREAS DOES NOT EXCEED
 THE WITH OF THE WALKWAY.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  