| 2019-05-06 20:32:18 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. |
| | |
| | 2. DEMOLITION OF THE EXISTING BUILDINGS. AN ASBESTOS |
| | SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT |
| | REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH |
| | COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963, |
| | OR BY EMAIL: [email protected] |
| | |
| | 3. UNITY OF TITLE. FOR ANY BUILDING CROSSING A PROPERTY |
| | LINE, EITHER A RECORDED UNITY OF TITLE, OR SOME OTHER |
| | APPROVED LEGAL INSTRUMENT, SHALL BE INCLUDED WITH THE |
| | PERMIT APPLICATION, OR THE BUILDING MUST HAVE A FIRE |
| | WALL ALONG THE PROPERTY LINE, PER SECTION 202 OF |
| | FLORIDA BUILDING CODE, BUILDING, FIRE SEPARATION |
| | DISTANCE. |
| | |
| | 4. EXIT STAIRS NOT DISCHARGING TO THE EXTERIOR OF THE |
| | BUILDING. GROUND FLOOR PLAN, SHEET A-1.1, SHOWS STAIR |
| | #1, #3 AND #4 ALL DISCHARGING INTERNAL TO THE BUILDING. |
| | SECTION 1028.1 OF FLORIDA BUILDING CODE, BUILDING, |
| | STATES THAT AT LEAST 50% OF THE REQUIRED EXITS SHALL |
| | DISCHARGE TO THE EXTERIOR OF THE BUILDING. THE ROUTE |
| | FROM STAIR #4 IS NOT CURRENTLY SHOWN AS A PROTECTED |
| | EXIT PASSAGEWAY. |
| | |
| | 5. LOCATION OF ACCESSIBLE PARKING SPACES. PER FAIR |
| | HOUSING ACT AND SECTION 208.3 OF FLORIDA ACCESSIBILITY |
| | CODE, ACCESSIBLE PARKING SPACES ARE TO BE LOCATED ON |
| | THE SHORTEST POSSIBLE ROUTE OF TRAVEL FROM ADJACENT |
| | PARKING TO AN ACCESSIBLE ENTRANCE. THE DESIGN OF |
| | ACCESSIBLE PARKING SPACES SHALL COMPLY WITH SECTION 502 |
| | OF FLORIDA ACCESSIBILITY CODE. THE FOLLOWING ACCESSIBLE |
| | PARKING SPACES ARE EITHER NOT USEABLE OR NOT LOCATED AS |
| | THE CLOSEST SPACE TO THE BUILDING ENTANCE: |
| | - SHEET A-1.2 ACCESSIBLE PARKING SPACE #61 IS NOT |
| | USABLE BECAUSE IT DOES NOT HAVE ACCESS TO ELEVATORS AS |
| | THE ELEVATORS ARE NO SHOW TO STOP ON THE 2ND LEVEL. |
| | - SHEET A-1.3 ACCESSIBLE PARKING SPACE #89 IS NOT |
| | USABLE BECAUSE THE ROUTE TO THE ELEVATOR GOES ACROSS |
| | THE STAIR LANDING AND THE LANDING DOORS DO NOT HAVE THE |
| | REQUIRED 48 INCH DOOR SWING SEPARATION REQUIRED BY |
| | SECTION 404.2.6 OF FLORIDA ACCESSIBILITY CODE. |
| | - SHEET A-1.4 ACCESSIBLE PARKING SPACE #171 IS NOT |
| | USABLE BECAUSE THE USER WOULD BE REQUIRED TO TRAVEL IN |
| | THE VEHICULAR DRIVE LANE TO GET TO THE ELEVATORS. |
| | - SHEET A-1.5 ACCESSIBLE PARKING SPACE #255 IS NOT |
| | USABLE BECAUSE THE ROUTE TO THE ELEVATOR GOES ACROSS |
| | THE STAIR LANDING AND THE LANDING DOORS DO NOT HAVE THE |
| | REQUIRED 48 INCH DOOR SWING SEPARATION REQUIRED BY |
| | SECTION 404.2.6 OF FLORIDA ACCESSIBILITY CODE. |
| | - SHEET A-1.4 ACCESSIBLE PARKING SPACE #320 IS NOT |
| | USABLE BECAUSE THE USER WOULD BE REQUIRED TO TRAVEL IN |
| | THE VEHICULAR DRIVE LANE TO GET TO THE ELEVATORS. |
| | - SHEET A-1.5 ACCESSIBLE PARKING SPACE #372 IS NOT |
| | USABLE BECAUSE THE ROUTE TO THE ELEVATOR GOES ACROSS |
| | THE STAIR LANDING AND THE LANDING DOORS DO NOT HAVE THE |
| | REQUIRED 48 INCH DOOR SWING SEPARATION REQUIRED BY |
| | SECTION 404.2.6 OF FLORIDA ACCESSIBILITY CODE. |
| | |
| | 6. VAN ACCESSIBLE PARKING SPACES. THE BUILDING DATA |
| | TABLE ON SHEET A-1.0 STATES THAT TWO VAN ACCESSIBLE |
| | PARKING SPACES ARE BEING PROVIDED BUT THE LOCATION OF |
| | THE TWO SPACES IS NOT SHOWN ON THE PLANS. PER SECTION |
| | 208.2.4 OF FLORIDA ACCESSIBILITY CODE, ONE IN EVERY SIX |
| | REQUIRED ACCESSIBLE SPACES (AT LEAST ONE) IN A PARKING |
| | STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND DESIGNED IN |
| | ACCORDANCE WITH SECTION OF 502 OF FLORIDA ACCESSIBILITY |
| | CODE (VERTICAL CLEARANCE NOT LESS THAN 98 INCHES AT |
| | SPACE AND VEHICULAR ACCESS ROUTE) |
| | |
| | 7. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, |
| | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR |
| | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, |
| | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE |
| | FLORIDA BUILDING CODE. |
| | |
| | 8. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES |
| | NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO |
| | MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL |
| | BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE |
| | EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED |
| | TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR |
| | OTHER APPROVED METHODS. |
| | |
| | 9. GREASE INTERCEPTOR. A GREASE INTERCEPTOR WILL BE |
| | REQUIRED. PLEASE CONTACT JEFFREY ODOMS, UTILITIES O&M |
| | SUPERINTENDENT, PUBLIC UTILITIES DEPARTMENT, FATS OILS |
| | AND GREASE DIVISION, AT (561) 822-2172, OR BY EMAIL: |
| | [email protected] |
| | |
| | 10. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS |
| | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE |
| | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED |
| | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, |
| | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND |
| | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, |
| | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. |
| | |
| | 11. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT |
| | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL |
| | HAVE A SEPARATE ADDRESS. FOR STREET ADDRESSING, CONTACT |
| | MICHAEL ORIO, GIS SUPPORT SPECIALIST, AT (561) 494 |
| | 1080, OR BY EMAIL: [email protected] |
| | |
| | 12. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT |
| | TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE |
| | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP |
| | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC |
| | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: |
| | [email protected] |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |