2020-03-25 08:08:02THE COMMENTS BELOW ARE FROM THE REVIEW OF THE MARCH 4,
 2020 SUBMITTAL PACKAGE.
  
 1. PERVIOUS/IMPERVIOUS AREA BREAKDOWN WAS ONLY PROVIDED
 FOR THE 16.28 ACRE PARCEL. THE SURVEY SHOWS DEVELOPMENT
 ON THE PROPOSED PARCEL 2 PARCEL. THE
 PERVIOUS/IMPERVIOUS AREA BREAKDOWN IS NEEDED FOR
 PROPOSED PARCEL 2.
  
 2. IN THE FEBRUARY 7, 2020 LOS ANALYSIS FOR FUTURE LAND
 USE AMENDMENT DOCUMENT BY CAULFIELD & WHEELER, INC.,
 UNDER THE PROPOSED ESTIMATED DRAINAGE FLOWS SECTION, IT
 WAS ASSUMED THE MAXIMUM PERCENT IMPERVIOUS AREA
 COVERAGE WAS 80%. ON THE PERVIOUS/IMPERVIOUS AREA MAP
 FOR PROPOSED PARCEL 1, THE PROPOSED PERVIOUS AREA IS
 LISTED AS 2.07 AC FOR THE 16.28 AC PARCEL WHICH
 CALCULATES TO BE 12.7% PERVIOUS. THE IMPERVIOUS AREA
 PERCENTAGE WOULD BE 87.3% WHICH EXCEEDS THE ASSUMPTION
 MADE IN THE DRAINAGE ANALYSIS. FUTURE DEVELOPMENT WILL
 NEED TO MEET IMPERVIOUS/PERVIOUS CRITERIA PER CITY
 CODE.
  
 3. ALLOWABLE DISCHARGE RATES WILL BE ESTABLISHED FOR
 EACH PARCEL BECAUSE THEY ARE SEPARATED BY THE LWDD
 RIGHT OF WAY.
  
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120