| 2019-02-12 20:39:22 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. |
| | |
| | 2. ACCESSIBLE ROUTE FOR PEDESTRIANS AND WHEELCHAIR |
| | USERS. THE SITE PLAN, SHEET 5 OF 6 SHOWS ONLY VEHICULAR |
| | ACCESS TO THE BUILDING. WHEN SUBMITTED FOR PERMIT, THE |
| | PLANS SHALL SHOW AT LEAST ONE ACCESSIBLE ROUTE, |
| | COMPLYING WITH SECTIONS 206.2 AND 402.2 OF FLORIDA |
| | ACCESSIBILITY CODE, FROM THE PUBLIC RIGHT-OF-WAY TO ALL |
| | ACCESSIBLE BUILDING OR FACILITY ENTRANCES. |
| | |
| | 3. ANY PART OF THE ABOVE-MENTIONED ACCESSIBLE ROUTE |
| | WITH A SLOPE GREATER THAN 1:20 SHALL BE CONSIDERED A |
| | RAMP AND SHALL COMPLY WITH SECTION 405 OF FLORIDA |
| | ACCESSIBILITY CODE. |
| | |
| | 4. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS |
| | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE |
| | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED |
| | FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, |
| | FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, |
| | GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, |
| | SITE IRRIGATION, ETC. |
| | |
| | 5. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT |
| | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL |
| | HAVE A SEPARATE ADDRESS. FOR STREET ADDRESSING, CONTACT |
| | MICHAEL ORIO, GIS SUPPORT SPECIALIST, AT (561) 494 |
| | 1080, OR BY EMAIL: [email protected] |
| | |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |