| 2018-12-04 13:18:42 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, |
| | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM |
| | BEACH FIRE RESCUE. |
| | |
| | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE |
| | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. |
| | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS |
| | ARE SUBMITTED FOR PERMIT. |
| | |
| | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE |
| | PROPOSED PROJECT. |
| | |
| | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE |
| | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A |
| | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED |
| | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN |
| | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY |
| | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER |
| | PROTECTION. |
| | |
| | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY |
| | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING |
| | ALL CONSTRUCTION ACTIVITIES. |
| | |
| | ANY GATES SHALL BE PROVIDED WITH KNOX KEY ACCESS LOCKS, |
| | PADLOCKS AND/OR SWITCHES FOR 24 HOUR EMERGENCY ACCESS. |
| | |
| | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM |
| | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. |
| | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND |
| | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT |
| | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. |
| | |
| | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE |
| | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE |
| | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. |
| | |
| | 5. THE CONSTRUCTION OF THE BUILDING(S) SHALL COMPLY |
| | WITH THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION |
| | CODE, INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE |
| | CODES. |
| | |
| | 6. NFPA 101, CHAPTER 30, NEW APARTMENT BUILDINGS SHALL |
| | BE USED WHEN REVIEWING THIS PROJECT FOR LIFE SAFETY. |
| | |
| | 7. A NFPA 13 COMPLIANT FIRE SPRINKLER SYSTEM IS |
| | REQUIRED FOR THIS STRUCTURE. A NFPA 14 COMPLIANT WET |
| | STANDPIPE SYSTEM MAY BE REQUIRED BASED ON THE LOWEST |
| | POINT OF FIRE DEPARTMENT ACCESS TO A 30FT FLOOR LEVEL. |
| | IN ADDITION, TEMPORARY STANDPIPES MAY BE REQUIRED WHEN |
| | A BUILDING REACHES THREE LEVELS OR THIRTY FEET WHILE |
| | BEING CONSTRUCTED. |
| | |
| | SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE SUBMITTED, |
| | REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU |
| | PRIOR TO ANY INSTALLATION. |
| | |
| | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, |
| | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. |
| | |
| | |
| | 8. A NFPA 72 COMPLIANT MONITORED FIRE ALARM SYSTEM IS |
| | REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP DRAWINGS, |
| | ARE REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY |
| | THE FIRE PREVENTION BUREAU PRIOR TO ANY INSTALLATION. |
| | |
| | 9. THE LOCATION OF THE FACP SHALL BE COORDINATED WITH |
| | THE OFFICE OF THE FIRE MARSHAL. |
| | |
| | 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL |
| | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL |
| | DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS, |
| | EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A |
| | PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE |
| | SAFETY FEATURES AND EQUIPMENT. |
| | |
| | ANY FABRICS/MATERIALS LOCATED ON THE EXTERIOR OF THE |
| | BUILDING SHALL COMPLY WITH THE FLORIDA FIRE PREVENTION |
| | CODE, LISTED AND TESTED AS APPLICABLE TO THE |
| | INSTALLATION, AND APPROVED THROUGH THE OFFICE OF THE |
| | FIRE MARSHAL. |
| | |
| | 11. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS |
| | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED |
| | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF |
| | FIRE PREVENTION. |
| | |
| | ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS |
| | DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE |
| | BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND |
| | FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET |
| | OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER |
| | ARRIVING EMERGENCY VEHICLES. |
| | |
| | 12. THERE DOES NOT APPEAR TO BE A DESIGNATED FIRE LANE |
| | FOR FD APPARATUS STAGING FOR THIS PROPOSED BUILDING. |
| | THE FIRE LANE WILL BE INDICATED AT THE OPTIMUM ACCESS |
| | POINT OF ARRIVING FIRE APPARATUS AND COORDINATED WITH |
| | THE FIRE HYDRANT, FCD, FACP, AND FD PERSONNEL ACCESS |
| | POINTS. THE LOCATION OF THE FIRE LANE SHALL BE |
| | COORDINATED WITH THE OFFICE OF THE FIRE MARSHAL. |
| | |
| | 13. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT |
| | DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. |
| | |
| | 14. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING |
| | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH |
| | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | |
| |