Plan Review Notes
Plan Review Notes For Project Z18100039
Project Number Z18100039
Review Stop STORM
Sequence Number 2
Notes
Date Text
2018-12-10 16:40:43THE FOLLOWING COMMENTS ARE FROM THE REIVIEW OF THE
 12/4/2018 SUBMITTAL PACKAGE:
  
 1. PROVIDE THE DIMENSION BETWEEN THE ADJACENT PARALLEL
 PARKING STRIPES ON THE STANDARD (PARKING) SPACE WITH
 WHEEL STOP DETAIL .
  
 2. THE VERTICAL DATUM ON THE SURVEY IS NAVD1988.
 PROVIDE THE RELATIONSHIP BETWEENNAVD1988 AND NGVD1929
 ON THE SURVEY.
  
 3. LIST THE VERTICAL DATUM ON EVERY ENGINEERING SHEET
 THAT SHOWS AN ELEVATION. THE VERTICAL DATUM SHOULD
 MATCH THE DATUM USED ON THE SURVEY AND PROVIDE THE
 CONVERSION EQUATION TO NGVD1929.
  
 4. SHEET C-500 (PAVING, GRADING AND DRAINAGE PLAN)
 INDICATES THE VERTICAL DATUM ON THE SHEET IS NGVD1929.
  
 5. CONSIDER ADDING ROOT BARRIERS BETWEEN THE TREES AND
 THE DRAINAGE PIPE(S).
  
 6. SHEET C-600: THE LEFT SIDE OF THE PIPE CONFLICT
 NOTES DID NOT PRINT.
  
 7. VERIFY INVERT ELEVATIONS FOR DRAINAGE STRUCTURES
 ST-01 AND ST-02.
  
 8. PROPOSED 3-STORY OFFICE ADDITION MAY BE WITHIN A
 SPECIAL FLOOD HAZARD AREA (SFHA). STRUCTURES WITHIN
 SFHA ARE TO HAVE A MINIMUM OF TWO FEET OF FREEBOARD
 ABOVE THE SFHA FLOOD ELEVATION.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]