| 2018-11-13 21:08:24 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. |
| | |
| | 2. DEMOLITION OF THE EXISTING BUILDINGS. AN ASBESTOS |
| | SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT |
| | REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH |
| | COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963, |
| | OR BY EMAIL: [email protected] |
| | |
| | 3. FLOOD ZONE. ACCORDING TO THE ADOPTED FLOOD INSURANCE |
| | RATE MAPS (FIRMS), THE PROPOSED BUILDING IS IN FLOOD |
| | ZONE AE, WITH A BASE FLOOD ELEVATION OF 7 FT NAVD. THE |
| | FIRST FLOOR OF THE BUILDING AND ALL ASSOCIATED |
| | MECHANICAL EQUIPMENT (CHILLERS, GENERATORS ETC.) SHALL |
| | BE 24 INCHES (FREEBOARD) ABOVE THE BASE FLOOD |
| | ELEVATION. |
| | |
| | 4. UNITY OF TITLE. FOR ANY BUILDING CROSSING A PROPERTY |
| | LINE, EITHER A RECORDED UNITY OF TITLE, OR SOME OTHER |
| | APPROVED LEGAL INSTRUMENT, SHALL BE INCLUDED WITH THE |
| | PERMIT APPLICATION, OR THE BUILDING MUST HAVE A FIRE |
| | WALL ALONG THE PROPERTY LINE, PER SECTION 202 OF |
| | FLORIDA BUILDING CODE, BUILDING, FIRE SEPARATION |
| | DISTANCE. |
| | |
| | 5. ALTERNATE ROUTE TO PUBLIC RIGHT OF WAY FROM WEST |
| | STAIR. SITE PLAN, SHEET A-1.0, SHOWS A SINGLE PAVED |
| | WALKWAY FROM THE WEST STAIR. BUILDING OCCUPANTS ARE |
| | COMPELLED TO WALK ALONGSIDE THE BUILDING WITHIN 10 FEET |
| | OF AREAS OF THE BUILDING THAT COULD BE THE SOURCE OF |
| | FIRE AND SMOKE AND PRESENT HIGH RISK TO PERSONS WITHIN |
| | 10 FEET OF THE BUILDING. PER SECTION 1028.5 OF THE |
| | FLORIDA BUILDING CODE THE EXIT DISCHARGE SHALL PROVIDE |
| | UNOBSTRUCTED ACCESS TO A PUBLIC RIGH OF WAY. AN |
| | ALTERNATIVE DIRECTIONAL CHOICE SHOULD BE PROVIDED FOR |
| | BUILDING OCCUPANTS TO GET FROM THE WEST STAIR TO THE |
| | PUBLIC RIGHT OF WAY. |
| | |
| | 6. VAN ACCESSIBLE PARKING SPACES. ONE IN EVERY SIX |
| | REQUIRED ACCESSIBLE SPACES (AT LEAST ONE) IN A PARKING |
| | STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND DESIGNED WITH |
| | VERTICAL HEADROOM NOT LESS THAN 98 INCHES AT SPACE AND |
| | VEHICULAR ACCESS ROUTE. |
| | |
| | 7. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, |
| | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR |
| | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, |
| | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE |
| | FLORIDA BUILDING CODE. |
| | |
| | 8. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND |
| | OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT, |
| | COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF |
| | OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF |
| | CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE |
| | VERIFIED. |
| | |
| | 9. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS |
| | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE |
| | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED |
| | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, |
| | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND |
| | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, |
| | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. |
| | |
| | 10. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT |
| | TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE |
| | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP |
| | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC |
| | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: |
| | [email protected] |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |