| 2018-11-13 17:32:49 | CASE NO. PB 1069Z |
| | KEISER UNIVERSITY DORMS |
| | 2600 NORTH MILITARY TRAIL |
| | |
| | - CONTACT ERIC SCHNEIDER @ (561) 822-1446 |
| | |
| | - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN |
| | WRITTEN FORMAT. |
| | |
| | - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF ELEVEN |
| | (11) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG FORMAT |
| | OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE |
| | RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS |
| | TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL |
| | COMMENTS. |
| | |
| | - THE PPRC COMMENTS SHALL BE SUFFICIENTLY ADDRESSED AND |
| | SUBMITTED TO THE PLANNING DIVISION BY 5 PM ON FRIDAY, |
| | NOVEMBER 30, 2018, TO BE ELIGIBLE TO BE SCHEDULED FOR |
| | THE JANUARY 15, 2019 PLANNING BOARD MEETING. |
| | |
| | - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT |
| | RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS |
| | FROM THE DATE OF THE PPRC MEETING (BY JANUARY 14, |
| | 2019), THE CASE SHALL BE CONSIDERED WITHDRAWN. ANY |
| | FURTHER ACTION SHALL REQUIRE A NEW DEVELOPMENT |
| | APPLICATION. |
| | |
| | - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) |
| | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED |
| | COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE |
| | APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE |
| | WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($600). |
| | |
| | - PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED |
| | IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION |
| | 94-39(I)(5) OF THE ZONING AND LAND DEVELOPMENT |
| | REGULATIONS. |
| | |
| | GENERAL |
| | |
| | 1) THERE IS A DISCREPANCY BETWEEN THE JUSTIFICATION |
| | STATEMENT/TRAFFIC STATEMENT AND THE PLANS. IS IT 200 OR |
| | 208 BEDS? |
| | |
| | 2) PLEASE CONSIDER INSTALLING SOLAR OR GREEN ROOF |
| | INSTALLATION ON THE ROOF OF THE PROPOSED DORMS. |
| | |
| | 3) PROVIDE DETAILS OF THE MECHANICAL EQUIPMENT SCREEN |
| | WALL. |
| | |
| | PARKING |
| | |
| | 4) THE PLANS INCLUDE A TAG FOR THE FUTURE LOCATION OF A |
| | PARKING STRUCTURE (#22). PLEASE NOTE THAT THE PARKING |
| | STRUCTURE MAY NOT BE BUILT ON THE 100 FOOT FPL |
| | EASEMENT, WHICH HAS MAJOR OVERHEAD POWER LINES. WAS THE |
| | #22 TAG SUPPOSED TO BE ON THE WEST SIDE OF THE FPL |
| | EASEMENT WHERE THERE IS ROOM TO CONSTRUCT A PARKING |
| | STRUCTURE? |
| | |
| | 5) THE PARKING SPACE TAGS SOUTH OF BUILDING #3 AND EAST |
| | OF THE DORMS ARE CONFUSING AS THEY OVERLAP THE TWO |
| | AREAS. AS THIS WILL BE THE PLAN OF RECORD, JUST INCLUDE |
| | THE FINAL NUMBER OF SPACES IN THIS AREA - 26 (18 |
| | SPACES/8 HC). |
| | |
| | 6) PROVIDE DETAILS OF THE FLUSH HEADER CURBS AND THE |
| | DROP CURB (VALLEY GUTTER). |
| | |
| | 7) THE PLANS SHOW A D CURB AT THE HEAD OF ALL THE |
| | PARKING SPACES. THE PARKING DETAIL SHOWS THE USE OF |
| | WHEEL STOPS. IT IS REDUNDANT TO USE BOTH. PLEASE |
| | CONSIDER PROVIDING A TWO FOOT OVERHANG OF THE D CURB TO |
| | PROVIDE MORE PERVIOUS AREA. |
| | |
| | BICYCLE PARKING |
| | |
| | 8) PLEASE CONSIDER INSTALLING ADDITIONAL BICYCLE AT THE |
| | LOCATION OF THE DORMS. EIGHT BICYCLE RACKS FOR 208 |
| | STUDENTS IS A VERY LOW NUMBER. ADDITIONALLY, PLEASE |
| | CONSIDER HAVING SOME OF THE BICYCLE RACKS UNDER COVER. |
| | |
| | 9) UPDATE SHEET C-2 TO STATE THAT EIGHT BICYCLE PARKING |
| | SPACES ARE PROVIDED (4 RACKS X 2 SPACES) AND THE |
| | PARKING TABLE ON SHEET MP.1 (64 PROVIDED). IF |
| | ADDITIONAL SPACE ARE PROVIDED BASED ON COMMENT #8 |
| | ABOVE, PLEASE UPDATE THE PLANS ACCORDINGLY. |
| | |
| | 10) PROVIDE THE DIMENSIONS OF THE BICYCLE RACK PAD ON |
| | THE SITE PLAN (SHEET C-2). |
| | |
| | SIDEWALKS |
| | |
| | 11) WIDEN THE SIDEWALKS AROUND THE DORMS TO A UNIFORM |
| | EIGHT FEET IN WIDTH AS THIS WILL BE A HEAVY PEDESTRIAN |
| | USE AREA. |
| | |
| | 12) PROVIDE A CONTINUOUS SIDEWALK ON THE SOUTH SIDE OF |
| | THE ENTRY DRIVE FROM THE DORMS TO THE SIDEWALK ADJACENT |
| | TO UNIVERSITY DRIVE (NORTH SIDE OF THE CANAL). THIS |
| | SIDEWALK CONNECTION WOULD BE AN ALMOST DIRECT ROUTE TO |
| | THE PEDESTRIAN ACCESS WAY TO THE VILLAGE COMMONS |
| | SHOPPING CENTER. |
| | |
| | DUMPSTER |
| | |
| | 13) PROVIDE THE DIMENSIONS OF THE GARBAGE ENCLOSURE ON |
| | THE PLANS. IT DOES NOT APPEAR TO CONFORM TO THE MINIMUM |
| | CITY STANDARDS. |
| | |
| | 14) PROVIDE A DETAIL OF THE ENCLOSURE WALLS. |
| | |
| | 15) PLEASE CONSIDER RECYCLING FACILITIES FOR THE DORMS. |
| | |
| |