2018-10-19 16:17:08THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 OCTOBER 10, 2018 REVIEW SUBMITTAL PACKAGE.
  
 1. NAVD TO NGVD CONVERSION EQUATION MISSING FROM THE
 SURVEY.
  
 2. MOVE THE YARD DRAINS AND ANY FLOOR GRATES OFF OF THE
 SOUTH PROPERTY LINE.
  
 3. TCE WILL LIKELY BE NEEDED FOR GROUT FILLING THE
 STORM PIPE UNDER THE BUILDING AT THE SOUTHEAST CORNER
 OF S. DIXIE HWY AND OKEECHOBEE BLVD.
  
 4. ADD A LABEL ON THE ENGINEERING PLANS FOR THE LINE
 WORK CONSISTING OF DASH LINE BETWEEN SMALL RECTANGLES.
 THE ENGINEERING PLANS SHOW AN EXISTING DRAINAGE PIPE
 CONNECTING TO THIS SYSTEM ON DIXIE HIGHWAY.
  
 5. THE SURVEY DOES NOT SHOW THE DRAINAGE MANHOLE THAT
 THE EXISTING DRAINAGE PIPE UNDER THE BUILDING MENTIONED
 IN #3 ABOVE CONNECTS TO AS SHOWN ON THE ENGINEERING
 PLANS. CONFIRM THERE IS AN EXISTING STRUCTURE OR IF ONE
 IS PROPOSED.
  
 6. AN EASEMENT WILL BE NEEDED FROM THE ADJACENT
 PROPERTY OWNER FOR THE PROPOSED DRAINAGE SYSTEM BETWEEN
 S-107 AND S-106 ON THEIR PROPERTY. DID YOU CONSIDER
 RUNNING A PIPE SOUTH OUT OF S-106 AND TYING INTO THE
 CURB INLET ON DIXIE HWY?
  
 7. WHY IS THERE A BREAK IN THE EXFILTRATION TRENCH
 BETWEEN S-104 AND S-105?
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120