Plan Review Notes
Plan Review Notes For Project Z18080013
Project Number Z18080013
Review Stop STORM
Sequence Number 1
Notes
Date Text
2018-09-12 13:25:48THE COMMENTS BELOW ARE FROM THE REVIEW OF THE AUGUST
 28, 2018 REVIEW PACKAGE:
  
 1. TOP PORTION OF SHEET C-500 MISSING.
  
 2. PROVIDE VERTICAL DATUM ON ALL SHEETS (I.E. C-400,
 C-500, C-600) THAT SHOW ELEVATIONS. IF VERTICAL DATUM
 IS NOT NGVD 1929 THEN A CONVERSION EQUATION TO
 CALCULATE NGVD 1929 ELEVATIONS SHALL ALSO BE PROVIDED.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120