Plan Review Notes
Plan Review Notes For Project Z18070021
Project Number Z18070021
Review Stop STORM
Sequence Number 2
Notes
Date Text
2019-10-29 16:26:33THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 OCTOBER 18, 2019 REVIEW SUBMITTAL PACKAGE. ADDITIONAL
 COMMENTS ARE BEING MADE ON THE 90% DESIGN SUBMITTAL
 CURRENTLY CITY PLAN REVIEW.
  
 THE ENGINEERING PLANS HAVE AN ISSUE DATE OF 10/11/2019
 AND INCLUDE:
 - DRAINAGE PLANS FOR 7TH STREET AND THE PROPOSED ALLEY
 (ROADNAME TO BE DETERMINED LATER),
 - GRADING PLAN FOR 7TH STREET, THE PROPOSED ALLEY AND
 THE INDIVISUAL LOTS BETWEEN 7TH STREET AND THE PROPOSED
 ALLEY
 - UTILITY PLANS (WATER MAIN ON 7TH STREET; GRAVITY
 SEWER IN THE PROPOSED ALLEY; AND UTILITY PLAN BLOW UP
 VIEWS).
  
 1. LABEL THE VERTICAL DATUM ON EACH SHEET WITH
 ELEVATION DATUM. THE CITY'S VERTICAL DATUM IS NGVD1929.
 THE CITY HAS ALLOWED THE USE OF NAVD1988 PROVIDED THE
 CONVERSION EQUATION BETWEEN NGVD1929 AND NAVD1988 IS
 PROVIDED ON THE SHEET.
  
 SHEET C403
 2. LABEL THE NORTH-SOUTH STREETS.
  
 3. PIPE SOUTH OF STRUCTURE SD-11 IS CALLED OUT AS 15"
 RCP. PIPE UPSTREAM OF THIS PIPE (SOUTH OF SD-20 ON
 SHEET C404) IS CALL OUT AS 18" RCP.
  
 4. STRUCTURE EX SD-8 IS SHOWN WITH EXISTING PIPES TO
 THE NE AND SW. THE SURVEY SHOWS THESE PIPES EXTENDING
 OUTSIDE THE RIGHT-OF-WAY. CONFIRM THE REMOVAL OF THESE
 PIPES WILL NOT AFFECT OFFSITE (I.E. OUTSIDE THE R/W)
 DRAINAGE. THIS COMMENT WILL APPLY TO ANY EXISTING PIPE
 THAT IS INDICATED TO BE REMOVED..
  
 5. DRAINAGE STRUCTURES WITHIN THE R/W SHOULD USE GRATES
 AND FRAMES/COVERS PER THE CITY'S STANDARD DETAILS.
  
 6. STORM DRAINAGE STRUCTURE TABLE - STRUCTURE SD-3 HAS
 AN INVERT ELEVATION OF 18.60 AND CONNECTED PIPE
 ELEVATION OF 20.60 S. WHICH IS CORRECT?
  
 7. LABEL THE PIPES IN THE PROFILE VIEW.
  
 8. IN THE PROFILE VIEW, WATER PIPES LARGER THAN 2" ARE
 LIKELY WATER MAINS AND NOT WATER SERVICES.
  
 9. IN PROFILE VIEW SHOW THE PIPE TO THE EAST OF EX
 SD-13 IN THE CORRECT ORIENTATION.
  
 10. SHOW THE EXISTING 4" GAS MAIN (KEYNOTE 11) IN THE
 PROFILE VIEW.
  
 11. ALL PROPOSED STORM PIPES WITHIN THE R/W SHOULD BE
 RCP (KEYNOTE #4).
  
 12. PROFILE PLAN AND PROFILE INFORMATION BETWEEN
 SAPODILLA AVE AND SD-4.
  
 13. PROVIDE PGL SLOPES.
  
 SHEET C404
 14. SHOW EXFILTRATION TRENCH IN PROFILE VIEW.
  
 15. PROVIDE PGL SLOPES.
  
 SHEET C503
 16. LINES TYPES IN THE LEGEND DO NOT MATCH PLAN.
  
 17. LABEL THE DASH-DOT LINES.
  
 18. CHECK SLOPES OF THE PROPOSED COURTYARD AREAS.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  
  
  
  