| 2018-08-07 18:42:27 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. |
| | |
| | 2. FLOOD ZONE. ACCORDING TO THE ADOPTED FLOOD INSURANCE |
| | RATE MAPS (FIRMS), THE PROPOSED BUILDING IS IN FLOOD |
| | ZONE AE, WITH A BASE FLOOD ELEVATION OF 12.7 FT NAVD. |
| | THE FIRST FLOOR OF THE BUILDING AND ALL ASSOCIATED |
| | MECHANICAL EQUIPMENT (CHILLERS, GENERATORS ETC.) SHALL |
| | BE 24 INCHES (FREEBOARD) ABOVE THE BASE FLOOD |
| | ELEVATION. |
| | |
| | 3. VAN ACCESSIBLE PARKING SPACES. PER SECTION 208.2.4 |
| | OF FLORIDA ACCESSIBILITY CODE, ONE IN EVERY SIX |
| | REQUIRED ACCESSIBLE SPACES (AT LEAST ONE) IN A PARKING |
| | STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND DESIGNED IN |
| | ACCORDANCE WITH SECTION OF 502 OF FLORIDA ACCESSIBILITY |
| | CODE (VERTICAL CLEARANCE NOT LESS THAN 98 INCHES AT |
| | SPACE AND VEHICULAR ACCESS ROUTE). THE PLANS SHALL SHOW |
| | AT LEAST TWO VAN ACCESSIBLE PARKING SPACES WHEN |
| | SUBMITTED FOR PERMIT. |
| | |
| | 4. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, |
| | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR |
| | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, |
| | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE |
| | FLORIDA BUILDING CODE. |
| | |
| | 5. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND |
| | OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT, |
| | COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF |
| | OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF |
| | CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE |
| | VERIFIED. |
| | |
| | 6. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES |
| | NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO |
| | MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL |
| | BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE |
| | EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED |
| | TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR |
| | OTHER APPROVED METHODS. |
| | |
| | 7. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS |
| | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE |
| | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED |
| | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, |
| | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND |
| | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, |
| | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. |
| | |
| | 8. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT |
| | TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE |
| | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP |
| | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC |
| | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: |
| | [email protected] |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |