| Plan Review Notes For Project Z18070011 |
| Project Number |
Z18070011 |
|
| Review Stop |
STORM |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-08-31 12:02:37 | THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE | | | AUGUST 29, 2018 SUBMITTAL REVIEW PACKAGE AND CAN BE | | | CONDITIONS OF SITE PLAN APPROVAL: | | | 1. THE CITY VERTICAL DATUM IS NGVD 1929. THE CITY HAS | | | ALLOWED THE USE OF NAVD 1988 PROVIDED THE CONVERSION | | | EQUATION TO NGVD 1929 IS PROVIDED. THIS CONVERSION | | | EQUATION IS NEEDED ON THE SPECIFIC PURPOSE SURVEY. | | | (REPEAT COMMENT). | | | | | | 2. ADD THE NAVD 1988 / NGVD 1929 CONVERSION EQUATION TO | | | THE SURVEY DATA ON SHEET C001. | | | | | | 3. LABEL THE VERTICAL DATUM ON THE ENGINEERING PLAN | | | SHEETS (C400 AND C401) AND PROVIDE THE CONVERSION | | | EQUATION BETWEEN NAVD 1988 AND NGVD 1929. | | | | | | 4.STORMWATER QUALITY TREATMENT TO BE PROVIDED FOR THE | | | NEW IMPERVIOUS AREAS IF THERE IS NOT EXISTING WATER | | | QUALITY TREATEMENT ALREADY PROVIDED IN A MASTER SYSTEM. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 | | | [email protected] | | | |
| |