| 2018-08-07 20:25:46 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. |
| | |
| | 2. ACCESSIBLE PARKING SPACES. SITE PLAN SHEET C300 |
| | STATES THAT THERE WILL BE 628 TOTAL PARKING SPACES AND |
| | ONLY 6 ACCESSIBLE PARKING SPACES. THERE ARE MORE |
| | ACCESSIBLE PARKING SPACES SHOWN ON THE PLANS BUT THE |
| | COUNT IN THE SITE DAT TABLE IS NOT CORRECT. 13 |
| | ACCESSIBLE PARKING SPACES ARE REQUIRED. THE MINIMUM |
| | NUMBER OF ACCESSIBLE PARKING SPACES PROVIDED SHALL BE |
| | IN ACCORDANCE WITH SECTION 208.2 OF FLORIDA |
| | ACCESSIBILITY CODE. |
| | |
| | 3. THE ADDITION TO THE EXISTING BUILDING IS COVERED BY |
| | CHAPTER 11 OF THE FLORIDA EXISTING BUILDING CODE. THE |
| | HEIGHT AND/OR AREA INCREASE DUE TO THE PROPOSED |
| | ADDITION SHALL NOT INCREASE THE TOTAL BUILDING HEIGHT |
| | AND/OR AREA BEYOND THAT ALLOWED UNDER THE APPLICABLE |
| | PROVISIONS OF CHAPTER 5 OF THE FLORIDA BUILDING CODE |
| | FOR THE TYPE OF CONSTRUCTION USED. |
| | |
| | 4. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS |
| | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE |
| | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED |
| | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, |
| | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND |
| | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, |
| | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. |
| | |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |