Plan Review Notes
Plan Review Notes For Project Z18060022
Project Number Z18060022
Review Stop TRAFFIC
Sequence Number 2
Notes
Date Text
2018-09-26 16:43:051309 SOUTH FLAGLER SEPTEMBER 6, 2018 SUBMITTAL
  
 - FLAGLER DR. DRIVEWAY GRADE IS EXTREMELY STEEP.
 DRIVEWAY PROFILE WILL NEED TO BE REVISED TO HAVE A
 GRADE BREAK OR VERTICAL CURVE INSERTED TO REDUCE
 BOTTOMING OUT IN SIDEWALK.
 - SHEET A1.01, EAST-WEST SECTION REFERENCES WRONG
 SHEET. CORRECT SECTION VIEW APPEARS TO BE ON SHEET
 A3-02 NOT A3-01.
 - A3-02 AND SHEET G0.04 HAVE DIFFERENT DRIVEWAY SLOPES.
 12% AND 11.3% RESPECTIVELY.
 - ADDITIONAL TRENCH DRAIN SHOULD BE PROVIDED AT FLAGLER
 DRIVEWAY AT RIGHT OF WAY LINE. STORMWATER SYSTEM NEEDS
 TO BE REVIEWED TO ENSURE WATER DOESN?T STAGE OUT OF
 THIS DRAIN.
 - FLAGLER DRIVE DRIVEWAY ? THE DRIVEWAY HORIZONTAL
 ALIGNMENT COULD USE SWITCHBACKS TO LESSEN THE GRADE OF
 THE DRIVEWAY. POTENTIALLY THE SWITCHBACK COULD BE USED
 TO DIRECT STORM WATER TO INLETS AND / OR ALLOW A
 GREATER FLAT AREA ON S. FLAGLER DR. LOMBARD STREET IN
 SAN FRANSISCO IS A GOOD PRECEDENT, ALTHOUGH CURVES ARE
 PROBABLY TOO SHARP FOR THE DESIGN VEHICLES.
 - SURVEY IS MISSING A UTILITY EASEMENT. ORB 25330,
 1318.
 - SURVEY IS NOT TO SCALE. ADDITIONAL COMMENTS MAY BE
 PROVIDED UPON RECEIPT OF A SCALED SURVEY DRAWING.
 - SHEET A3-01 SHOWS SLOPE DRAINING DIRECTLY ON ACACIA.
 CIVIL PLANS SHOW DIFFERENT GRADING IN THIS AREA. RUNOFF
 DIRECTLY ONTO ACACIA ISN?T ALLOWED. REVISE PLAN SET TO
 BE CONSISTENT.
 - ACACIA - PROPOSED LANDSCAPING DOES NOT APPEAR TO BE
 FEASIBLE DUE TO THE NUMBER OF UNDERGROUND UTILITIES.
 - CURRIE CRESCENT ENTRANCE. A GATE IS SHOWN SHEET A0.01
 FOR THE LOADING ENTRY. PROVIDE ADDITIONAL DETAIL ON THE
 LOCATION OF THE GATE. THE GATE SHOULD BE PLACED 20?
 BACK FROM THE RIGHT OF WAY LINE. NOTE IT IS ILLEGAL
 UNDER FLORIDA STATUTE AND CITY CODE FOR A VEHICLE TO
 STOP OR STAND ON THE SIDEWALK.
 - TRANSPORTATION STAFF DOES NOT SUPPORT THE PROPOSED
 BACKUP MANEUVER FROM THE CURRIE CRESCENT ENTRANCE. A
 WAIVER WILL BE REQUIRED.
 - TRANSPORTATION DIVISION REQUESTS A WIDER SIDEWALK ON
 FLAGLER DRIVE OR A MEANDERING SIDEWALK SIMILAR TO WHAT
 HAS BEEN CONSTRUCTED TO THE NORTH OF THE PROJECT AT
 1101 S. FLAGLER DRIVE.
 - ACACIA DRIVE - THE PROPOSED ART WALK DESIGN WILL
 HINDER EMERGENCY VEHICLE ACCESS AND POTENTIALLY ACCESS
 TO THE EXISTING PARKING SPACES AND RESIDENTIAL BUILDING
 AT THE REAR OF 1301 S. FLAGLER DRIVE. THE DESIGN SHOULD
 BE MODIFIED TO ACCOMMODATE TURNING MOVEMENTS FROM 1301
 S. FLAGLER DRIVE?S DRIVE TO THE REAR OF 1301 S.
 FLAGLER'S PROPERTY.
 - CONTRIBUTION OR CONSTRUCTION OF A RAPID RECTANGULAR
 FLASHING BEACON (RRFB) AND DECORATIVE CROSSWALK ON S.
 FLAGLER DR. IS REQUESTED. LOCATION TO BE DETERMINED.
 JUST NORTH OF ACACIA IS A POTENTIAL LOCATION AS A
 MID-BLOCK REFUGE COULD BE PROVIDED IN THE EXISTING
 GORED OUT MEDIAN AREA.
  
 ERIK D. FERGUSON, PE
 CITY TRANSPORTATION ENGINEER
  