| Date |
Text |
| 2018-07-10 21:03:08 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. |
| | |
| | 2. DEMOLITION OF THE EXISTING BUILDING. AN ASBESTOS |
| | SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT |
| | REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH |
| | COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963, |
| | OR BY EMAIL: [email protected] |
| | |
| | 3. FLOOD ZONE. ACCORDING TO THE ADOPTED FLOOD INSURANCE |
| | RATE MAPS (FIRMS), THE PROPOSED BUILDING IS IN FLOOD |
| | ZONE AE, WITH A BASE FLOOD ELEVATION OF 7 FT NAVD. THE |
| | FIRST FLOOR OF THE BUILDING AND ALL ASSOCIATED |
| | MECHANICAL EQUIPMENT (CHILLERS, GENERATORS ETC.) SHALL |
| | BE 24 INCHES (FREEBOARD) ABOVE THE BASE FLOOD |
| | ELEVATION. |
| | |
| | 4. UNITY OF TITLE. FOR ANY BUILDING CROSSING A PROPERTY |
| | LINE, EITHER A RECORDED UNITY OF TITLE, OR SOME OTHER |
| | APPROVED LEGAL INSTRUMENT, SHALL BE INCLUDED WITH THE |
| | PERMIT APPLICATION, OR THE BUILDING MUST HAVE A FIRE |
| | WALL ALONG THE PROPERTY LINE, PER SECTION 202 OF |
| | FLORIDA BUILDING CODE, BUILDING, FIRE SEPARATION |
| | DISTANCE. |
| | |
| | 5 ANY PART OF AN ACCESSIBLE ROUTE WITH A SLOPE GREATER |
| | THAN 1:20 SHALL BE CONSIDERED A RAMP AND SHALL COMPLY |
| | WITH SECTION 405 OF FLORIDA ACCESSIBILITY CODE. |
| | |
| | 6. PASSENGER LOADING/VALET DROP-OFF. GROUND FLOOR PLAN |
| | A1.01 SHOWS THREE PARKING SPACES THAT APEAR TO BE VALET |
| | CAR DROP=OFF. NONE OF THESE SPACES ARE ACCESSIBLE, SO |
| | THE BUILDING ENTRANCE MUST HAVE A PASSENGER LOADING |
| | ZONE IN COMPLIANCE WITH SECTION 209.4 OF FLORIDA |
| | ACCESSIBILITY CODE, AS AN ALTERNATIVE FOR VALET |
| | DROP-OFF. |
| | |
| | 7 . VAN ACCESSIBLE PARKING SPACES. PER SECTION 208.2.4 |
| | OF FLORIDA ACCESSIBILITY CODE, ONE IN EVERY SIX |
| | REQUIRED ACCESSIBLE SPACES (AT LEAST ONE) IN A PARKING |
| | STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND DESIGNED IN |
| | ACCORDANCE WITH SECTION OF 502 OF FLORIDA ACCESSIBILITY |
| | CODE (VERTICAL CLEARANCE NOT LESS THAN 98 INCHES AT |
| | SPACE AND VEHICULAR ACCESS ROUTE) |
| | |
| | 8. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, |
| | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR |
| | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, |
| | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE |
| | FLORIDA BUILDING CODE. |
| | |
| | 9. EXIT DISCHARGE. SITE PLAN SHEET A0.01 SOWS AN |
| | INSWING GATE FROM THE REAR (WEST) STAIR TO THE CURRIE |
| | CRESCENT SIDE WALK. THE GATE MSUT BE AN OUTSWING GATE, |
| | |
| | 10. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE |
| | DOES NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL |
| | OPENINGS TO MEET THE DEFINITION OF AN OPEN PARKING |
| | GARAGE, IT WILL BE CONSIDERED AN ENCLOSED PARKING |
| | GARAGE AND MUST HAVE EXHAUST SYSTEMS. THE EXHAUST |
| | SYSTEMS SHALL BE DESIGNED TO MINIMIZE NOISE LEVELS |
| | USING INLINE FAN SILENCERS OR OTHER APPROVED METHODS. |
| | |
| | 11. GREASE INTERCEPTOR. PODIUM LEVEL 2 PLAN, SHEET |
| | A1.02, SHOWS A CHEF'S KITCHEN. A GREASE INTERCEPTOR MAY |
| | BE REQUIRED. PLEASE CONTACT JEFFREY ODOMS, UTILITIES |
| | O&M SUPERINTENDENT, PUBLIC UTILITIES DEPARTMENT, FATS |
| | OILS AND GREASE DIVISION, AT (561) 822-2172, OR BY |
| | EMAIL: [email protected] |
| | |
| | 12. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS |
| | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE |
| | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED |
| | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, |
| | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND |
| | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, |
| | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. |
| | |
| | 13 ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT |
| | TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE |
| | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP |
| | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC |
| | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: |
| | [email protected] |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |