| 2018-06-06 09:06:03 | GENERAL COMMENTS: |
| | |
| | 1.) THERE SEEMS TO BE AN ISSUE WITH THE TEXT (TEXT |
| | ERROR) THROUGHOUT THE PLAN SET. THIS MUST BE CORRECTED. |
| | |
| | |
| | SITE PLAN: |
| | |
| | 1.) PLEASE MAKE THE FOLLOWING CORRECTIONS IN THE ZONING |
| | CHART (SHEET G-2): BUILDING FRONTAGE REFERENCE IS SEC. |
| | 94-215(H)(2) TABLE VII-6 (NOT SEC. 94-215(H)(2) TABLE |
| | VII-6&7); OFFICE SPACE PROVIDED IS 1,902 SQ. FT. (NOT |
| | 1,995 SQ. FT.) |
| | |
| | 2.) THERE SEEMS TO BE A CONFLICT WITH THE BUILDING |
| | FRONTAGE NOTED ON POINSETTIA AVENUE. THERE ARE SHEETS |
| | THAT HAVE A 5'-0" SETBACK AND SHEETS THAT HAVE A 5'-1" |
| | SETBACK IN THE PLAN SET. THIS MUST BE ADDRESSED ON ALL |
| | SHEETS (INCLUDING THE ZONING CHART, SHEET G-2) FOR |
| | CONSISTENCY. |
| | |
| | 3.) THERE IS A 12'-9" SETBACK NOTED ON SHEET A-1.1. |
| | PLEASE ADDRESS/CORRECT. |
| | |
| | 4.) CORRECT KNOX (NOT KNX) FOR GENERAL NOTES #7 ON |
| | SHEET A-0.1. |
| | |
| | |
| | INSTRUCTIONS FOR RESUBMITTAL: |
| | |
| | * PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN |
| | WRITTEN FORMAT. |
| | |
| | * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF SIX |
| | (6) PAPER COPIES, ONE (1) REDUCED COPY IN 8.5 INCHES X |
| | 11 INCHES AND ONE (1) SET IN 11 INCHES X 17 INCHES, AND |
| | AN ELECTRONIC COPY OF ALL PLANS. |
| | |
| | * PLEASE NOTE THAT CHANGES ON THE RESUBMITTED PLANS MAY |
| | RESULT IN ADDITIONAL COMMENTS. |
| | |
| | * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) |
| | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED |
| | COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE |
| | APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE |
| | WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE. |
| | |