Plan Review Notes
Plan Review Notes For Project Z18050030
Project Number Z18050030
Review Stop STORM
Sequence Number 4
Notes
Date Text
2019-07-31 15:41:26THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE JULY
 17, 2019 REVIEW PACKAGE. THEY CAN BE PROVISO FOR SITE
 PLAN APPROVAL.
  
 1.. PROVIDE CONDITION ASSESSMENT OF THE EXISTING
 DRAINAGE SYSTEM ON N. ROSEMARY AVE. [REPEAT COMMENT]
  
 2.. THERE SHOULD NOT BE DIRECT SHEETFLOW RUNOFF ACROSS
 THE SIDEWALK ALONG THE NORTH SIDE OF 8TH STREET.GRADE
 THE PARCEL NORTH OF 8TH STREET TO FLOW INTO THE
 PERVIOUS BANDS TO OBTAIN SOME STORMWATER TREATMENT.YARD
 DRAIN(S) CAN BE CONSTRUCTED TO COLLECT EXCESS
 STORMWATER AND PIPE IT TO THE EXISTING DRAIANGE
 STRUCTURE AT THE NW CORNER OF 8TH ST AND N. ROSEMARY
 AVE.
  
 3. PRIOR TO C.O., THE PROPOSED EASEMENTS SHALL BE
 RECORDED IN THE COUNTY CLERK'S OFFICE.
  
 4. LANDSCAPE PLAN DOES NOT MATCH THE SITE/HARDSCAPE
 PLAN. THE ONSITE CIRCULAR BANDS NORTH OF 8TH STREET
 MEASURE 5 FEET WIDE ON THE LANDSCAPE PLAN. THE BANDS
 ARE DIMENSIONED AS 4 FEET WIDE ON THE HARDSCAPE PLAN.
  
 5. 8TH STREET IMPROVEMENTS SHOULD BE COORDINATED WITH
 THE HEART AND SOUL PROJECT.
  
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120
  