| 2018-06-08 13:37:23 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, |
| | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM |
| | BEACH FIRE RESCUE. |
| | |
| | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE |
| | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. |
| | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS |
| | ARE SUBMITTED FOR PERMIT. |
| | |
| | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE |
| | PROPOSED PROJECT. |
| | |
| | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE |
| | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A |
| | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED |
| | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN |
| | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY |
| | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER |
| | PROTECTION. |
| | |
| | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY |
| | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING |
| | ALL CONSTRUCTION ACTIVITIES. |
| | |
| | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM |
| | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. |
| | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND |
| | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT |
| | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. |
| | |
| | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE |
| | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE |
| | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. |
| | |
| | 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH |
| | THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE, |
| | INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES. |
| | |
| | 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE |
| | OCCUPANCY TYPE, PER THE FLORIDA FIRE PREVENTION CODE. |
| | |
| | 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE |
| | LOAD CALCULATION IS INCLUDED AND THAT ADEQUATE WATER |
| | SUPPLY IS EXISTING OR WILL BE PROVIDED. |
| | |
| | 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS |
| | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED |
| | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF |
| | FIRE PREVENTION. |
| | |
| | 9. IF APPLICABLE FOR THE OCCUPANCY REQUIREMENTS, |
| | PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER THE |
| | APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY |
| | ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM, |
| | ENSURE THEY COMPLY WITH THE REQUIREMENTS OF FS 61G AND |
| | SUBMITTED WITH THE MASTER PLAN. |
| | |
| | 10. A COMPLETE LIFE SAFETY PLAN SHALL BE PROVIDED THAT |
| | ILLUSTRATE OCCUPANT LOADS, TRAVEL DISTANCES, COMMON |
| | PATHS OF TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, |
| | EMERGENCY LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE |
| | EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES |
| | AND EQUIPMENT. |
| | |
| | 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE |
| | SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY |
| | DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS. |
| | |
| | 12. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT |
| | DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL. |
| | |
| | 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING |
| | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH |
| | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. |
| | |
| | |
| | PETER LEDUC |