| 2018-06-12 18:56:10 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. |
| | |
| | 2. FLOOD ZONE. ACCORDING TO THE ADOPTED FLOOD INSURANCE |
| | RATE MAPS (FIRMS), THE PROPOSED BUILDING IS IN FLOOD |
| | ZONE AE, WITH A BASE FLOOD ELEVATION OF 12.2 FT NAVD. |
| | THE FIRST FLOOR OF THE BUILDING AND ALL ASSOCIATED |
| | MECHANICAL EQUIPMENT (CHILLERS, GENERATORS ETC.) SHALL |
| | BE AT OR ABOVE 14.2 FT NAVD TO MEET THE FREEBOARD |
| | REQUIREMENT OF 2 FEET ABOVE THE BASE FLOOD ELEVATION. |
| | |
| | 3. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, |
| | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR |
| | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, |
| | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE |
| | FLORIDA BUILDING CODE. |
| | |
| | 4. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS |
| | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE |
| | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED |
| | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, |
| | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND |
| | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, |
| | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. |
| | |
| | 5. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT |
| | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL |
| | HAVE A SEPARATE ADDRESS. FOR STREET ADDRESSING, CONTACT |
| | MICHAEL ORIO, GIS SUPPORT SPECIALIST, AT (561) 494 |
| | 1080, OR BY EMAIL: [email protected] |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |