| 2018-06-01 16:49:42 | GENERAL COMMENTS: |
| | |
| | 1.) PLEASE ENSURE ALL PLAN PACKETS HAVE A SIGNED AND |
| | SEALED SURVEY. |
| | |
| | 2.) DISCUSSION REGARDING THE INTERNAL PEDESTRIAN |
| | CROSSWALK MUST OCCUR PRIOR TO PLANNING BOARD. |
| | |
| | |
| | MASTER DEVELOPMENT PLAN (SHEET MP-1) COMMENTS: |
| | |
| | 1.) THE FUTURE PROPOSED HOTEL USE HAS AN FAR OF 0.21, |
| | WHICH MEANS THAT A MAXIMUM BUILDING POTENTIAL OF 80,836 |
| | SQ. FT. HAS BEEN ESTABLISHED FOR THE USE. THIS MAXIMUM |
| | BUILDING POTENTIAL SHOULD BE REFERENCED IN THE OVERALL |
| | DEVELOPMENT SITE DATA TABULAR AND IN THE MASTER |
| | DEVELOPMENT SITE PLAN. |
| | |
| | 2.) TRACT #2 IN THE MASTER DEVELOPMENT SITE PLAN SHALL |
| | REFLECT THE LATEST CHANGES APPROVED BY THE TPS LETTER |
| | ISSUED ON APRIL 4, 2018, BY THE PALM BEACH COUNTY |
| | DEPARTMENT OF PUBLIC WORKS AND ENGINEERING - TRAFFIC |
| | DIVISION. (I.E. BUILDING POTENTIAL OF UP TO 2,420 SQ. |
| | FT. FOR THE PROPOSED RESTAURANT PARCEL) |
| | |
| | 3.) THE HEADER WITHIN THE PLAN SHOULD REFERENCE PALMS |
| | GATEWAY COMMERCIAL PLANNED DEVELOPMENT (NOT EXTRA SPACE |
| | STORAGE). PLEASE ADDRESS. |
| | |
| | |
| | SITE PLAN COMMENTS: |
| | |
| | 1.) BICYCLE RACK SHALL BE LOCATED NEAR THE ENTRANCE OF |
| | THE BUILDING AS PRACTICABLE. [ZLDR S.94-485(Q)] |
| | [5/18/18 PPRC COMMENT NOT ADDRESSED] |
| | |
| | 2.) THE DETAIL OF THE DUMPSTER ENCLOSURE DOES NOT MEET |
| | THE MINIMUM DIMENSIONAL STANDARDS OF THE ZLDRS. PLEASE |
| | ADDRESS. [ZLDR S.94-315] |
| | |
| | 3.) WITH REFERENCE TO PPRC RESPONSE #1 (RESUBMITTAL |
| | DATED 5/25/2018), RAISED LANDSCAPE PLANTERS WILL BE |
| | PROVIDED ALONG THE OUTDOOR SEATING AREA. PLEASE INCLUDE |
| | A DETAIL OF THE PROPOSED PLANTERS IN THE PLAN PACKET. |
| | |
| | 4.) PLEASE PROVIDE DIMENSIONS FOR THE PROPOSED LOADING |
| | ZONE IN THE SITE PLAN. IT SHOULD BE NOTED THAT THE |
| | DIMENSIONS PROVIDED IN THE TABULAR DOES NOT MATCH THE |
| | DIMENSIONS MEASURED IN THE SITE PLAN. PLEASE ADDRESS |
| | FOR CONSISTENCY. |
| | |
| | 5.) SHOW THE PROPOSED LIGHT POLE FIXTURES IN THE SITE |
| | PLAN. PLEASE ENSURE THAT THE LOCATION OF THE POLES ARE |
| | CONSISTENT WITH THE PHOTOMETRIC PLAN. ALSO, DEMONSTRATE |
| | THAT THE POLES WILL NOT INTERFERE WITH VEHICULAR |
| | PARKING/MOVEMENT BY PROVIDING A DETAIL OF THE PARKING |
| | STALL STRIPING AND THE LOCATION OF THE POLE FIXTURE. |
| | |
| | 6.) CHECK DIMENSIONS FOR THE HANDICAPPED AND STANDARD |
| | PARKING STALLS IN THE SITE DATA TABULAR. THERE SEEMS TO |
| | BE INCORRECT INFORMATION PROVIDED ON THE DIMENSIONS. |
| | |
| | 7.) WHY IS THERE A GARBAGE CAN AND BENCH DETAIL IN THE |
| | PLANS ON SHEET D-1? THERE DOES NOT SEEM TO BE ANY |
| | BENCHES OR GARBAGE CAN PROVIDED ON THE RESTAURANT |
| | PARCEL. |
| | |
| | |
| | LANDSCAPE (SHEETS L-1 AND L-2) COMMENTS: |
| | |
| | 1.) THE WALLS OF THE DUMPSTER ENCLOSURE SHALL BE FULLY |
| | LANDSCAPED WITH SHRUBS AND HEDGES PLANTED AT 2 FT. |
| | INTERVALS. [ZLDR S.94-315] [5/18/18 PPRC COMMENT NOT |
| | ADDRESSED] |
| | |
| | 2.) SHOW ALL LANDSCAPE BUFFERS THAT HAD PREVIOUSLY BEEN |
| | APPROVED FOR THE CPD. THIS INFORMATION IS MISSING FROM |
| | THE CURRENT SUBMITTAL. [5/18/18 PPRC COMMENT NOT |
| | ADDRESSED] |
| | |
| | 3.) ADDITIONAL COMMENTS TO BE PROVIDED BY THE CITY'S |
| | LANDSCAPE PLANNER. |
| | |
| | |
| | ARCHITECTURAL PLANS (FLOOR PLAN AND ELEVATIONS): |
| | |
| | 1.) APPLICANT HAD NOTED THAT MECHANICAL EQUIPMENT, SUCH |
| | AS THE A/C UNIT, WILL BE LOCATED ON THE ROOFTOP OF THE |
| | PROPOSED RESTAURANT BUILDING; HOWEVER, IT IS NOT CLEAR |
| | TO HOW THE MECHANICAL EQUIPMENT WILL BE SCREENED FROM |
| | PUBLIC VIEW. PLEASE DEMONSTRATE HOW THE MECHANICAL |
| | EQUIPMENT WILL BE SCREENED. AT MINIMUM, THERE SHOULD BE |
| | A NOTE IN THE PLANS THAT ALL MECHANICAL EQUIPMENT WILL |
| | BE SCREENED FROM VIEW BY THE BUILDING PARAPET OR WALL. |
| | |
| | PHOTOMETRICS: |
| | |
| | 1.) LOCATION OF LIGHT FIXTURES SHALL BE PROVIDED ON ALL |
| | PLANS FOR CONSISTENCY AND TO ENSURE THAT THE FIXTURES |
| | ARE NOT BE IN CONFLICT WITH EXISTING/PROPOSED SITE |
| | ELEMENTS. [5/18/18 PPRC COMMENT NOT ADDRESSED] |
| | |
| | |
| | INSTRUCTIONS FOR RESUBMITTAL: |
| | |
| | * PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN |
| | WRITTEN FORMAT. |
| | |
| | * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF |
| | FIFTEEN (15) PAPER COPIES, ONE (1) REDUCED COPY IN 8.5 |
| | INCHES X 11 INCHES AND ONE (1) SET IN 11 INCHES X 17 |
| | INCHES, AND AN ELECTRONIC COPY OF ALL PLANS. PLEASE |
| | NOTE THAT CHANGES ON THE RESUBMITTED PLANS MAY RESULT |
| | IN ADDITIONAL COMMENTS. |
| | |
| | * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) |
| | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED |
| | COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE |
| | APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE |
| | WILL BE 20 PERCENT ($600) OF THE ORIGINAL APPLICATION |
| | FEE. [NOTE: THE $600 RESUBMITTAL FEE WILL APPLY TO THE |
| | NEXT RESUBMITTAL] |
| | |
| | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE |
| | QUESTIONS. |
| | |
| |