Plan Review Notes
Plan Review Notes For Project Z18040013
Project Number Z18040013
Review Stop TRAFFIC
Sequence Number 1
Notes
Date Text
2018-05-08 16:57:15- PROVIDE TRAFFIC IMPACT STUDY IN ACCORDANCE WITH CITY
 CODE SECTION 94-311 OR DOCUMENTATION DEMONSTRATING THAT
 CITY CODE SECTION 94-311(C) TRAFFIC IMPACT STUDY
 REQUIRED IS NOT APPLICABLE.
 - PROVIDE TRIP GENERATION LETTER DEMONSTRATING THAT
 DRIVEWAY VOLUME IS LOW ENOUGH TO WARRANT TWO WAY YIELD
 OPERATION
 - PARKING SPACE WIDTH SHOULD BE INCREASED TO 9?-6? TO
 ALLOW FOR CAR DOOR OPENING NEXT TO WALL. STANDARD
 PARKING SPACE IN CITY CODE DOES NOT ASSUME A WALL IS
 ADJACENT TO THE PARKING SPACE.
 - 15?-5? STACKING DISTANCE TO GATE IS INSUFFICIENT.
 PROVIDE 20? STACKING DISTANCE. IT IS ILLEGAL UNDER
 FLORIDA STATUTES FOR A VEHICLE TO STAND ON THE
 SIDEWALK.
 - SHOW ADA RAMPS IN DRIVEWAY
 - REVIEW IS PRELIMINARY BASED ON LIMITED INFORMATION
 PROVIDED ON SITE PLAN. DETAILED ENGINEERING PLANS WILL
 BE REQUIRED.
 ERIK D. FERGUSON, PE
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  