Plan Review Notes
Plan Review Notes For Project Z18040013
Project Number Z18040013
Review Stop B
Sequence Number 1
Notes
Date Text
2018-05-08 18:53:54DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. ACCORDING TO THE ADOPTED FLOOD INSURANCE RATE MAPS
 (FIRMS), THE PROPOSED BUILDING IS IN FLOOD ZONE AE WITH
 A BASE FLOOD ELEVATION OF 12.1 FT NAVD. THE FIRST FLOOR
 OF THE BUILDING AND ALL ASSOCIATED MECHANICAL EQUIPMENT
 (CHILLERS, GENERATORS ETC.) SHALL BE 24 INCHES
 (FREEBOARD) ABOVE THE BASE FLOOD ELEVATION.
  
 3. PEDESTRIAN/WHEELCHAIR ACCESSIBLE ROUTE. THE PLANS
 ONLY SHOW VEHICLULAR DRIVEWAY ACCESS AND DO NOT SHOW
 ANY PEDESTRIAN ACCESS TO THE FACILITY. WHEN SUBMITTED
 FOR PERMIT, THE PLANS SHALL SHOW AT LEAST ONE
 ACCESSIBLE ROUTE, COMPLYING WITH SECTIONS 206.2 AND
 402.2 OF FLORIDA ACCESSIBILITY CODE, FROM THE PUBLIC
 RIGHT-OF-WAY TO ALL ACCESSIBLE BUILDING OR FACILITY
 ENTRANCES.
  
 4. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 5. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND
 OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT,
 COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF
 OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF
 CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE
 VERIFIED.
  
 6. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS,
 FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS,
 GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE,
 SITE IRRIGATION, ETC.
  
 7. EACH SEPARATE BUILDING, AND UNIT WITH AN INDEPENDENT
 ENTRANCE FROM THE STREET, SHALL HAVE A SEPARATE
 ADDRESS. FOR STREET ADDRESSING, CONTACT MICHAEL ORIO,
 GIS SUPPORT SPECIALIST, AT (561) 494 1080, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  