Plan Review Notes
Plan Review Notes For Project Z18030023
Project Number Z18030023
Review Stop Z
Sequence Number 2
Notes
Date Text
2019-05-29 16:12:14GENERAL COMMENTS:
  
 1.) THE SURVEY SUBMITTED WITH THE APPLICATION IS A COPY
 AND IS OUTDATED (DATED 12/14/16). PLEASE PROVIDE AN
 UPDATED SURVEY OF THE PROPERTY. THE SURVEY MUST BE
 ABSTRACTED, SIGNED, DATED AND SEALED BY A FLORIDA
 REGISTERED LAND SURVEYOR. THE SURVEY MUST ALSO
 ACCURATELY REFLECT WHAT IS EXISTING ON THE PROPERTY AND
 IMMEDIATE SURROUNDING AREAS (I.E. THERE SEEMS TO BE AN
 EXISTING FIRE HYDRANT ON BISCAYNE DRIVE THAT IS NOT
 REFLECTED IN THE SURVEY OR THE SITE AND LANDSCAPE PLAN;
 HOWEVER, IT IS REFLECTED IN THE CIVIL PLANS). [5/4/2018
 REPEAT COMMENT]
  
 2.) THE PROPOSAL REQUIRES THE APPROVAL OF PB CASE NO.
 1751 (ABANDONMENT OF A PORTION OF BISCAYNE DRIVE, JUST
 WEST OF THE FEC RAILROAD). PB 1751 IS CURRENTLY PENDING
 WITH THE PLANNING DIVISION, AS THE TURNAROUND ON
 BISCAYNE DRIVE MUST BE RESOLVED TO STAFF?S SATISFACTION
 PRIOR TO THE ABANDONMENT APPLICATION MOVING FORWARD.
 [5/4/2018 REPEAT COMMENT - STAFF DOES NOT BELIEVE THIS
 ISSUE HAS BEEN RESOLVED. DOCUMENTATION FROM THE
 ENGINEERING DEPARTMENT IS ALSO REQUIRED TO VERIFY THAT
 THE ISSUE HAS BEEN RESOLVED.]
  
  
 SITE PLAN COMMENTS:
  
 1.) IT IS UNCERTAIN IF THE DRIVE/TURNAROUND ON THE
 SOUTH SIDE OF BISCAYNE DRIVE, LOCATED ON THE ADJACENT
 SINGLE-FAMILY RESIDENTIAL LOT IS EXISTING/HAS BEEN
 MODIFIED. THIS MUST BE CLARIFIED IN THE PLANS. ANY USE
 OF THE RESIDENTIAL PROPERTY FOR ANY VEHICULAR
 TURN-AROUND IS STRICTLY PROHIBITED. [5/4/2018 REPEAT
 COMMENT]
  
 2.) PROVIDE WRITTEN DOCUMENTATION FROM SANITATION THAT
 THE LOCATION OF THE DUMPSTER ENCLOSURE IS ADEQUATE.
  
 3.) A NEW LIFT STATION WAS DESIGNED AT THE SAME
 LOCATION OF THE PROPOSED DUMPSTER ENCLOSURE, PER THE
 ORIGINAL SUBMITTAL (RECEIVED 3/13/2018). WHAT HAPPENED
 TO THE LIFT STATION? IT SEEMED TO HAVE DISAPPEARED FROM
 THE PLANS (I.E. HAS IT BEEN RELOCATED AND IF SO,
 WHERE?).
  
 4.) THE BICYCLE RACK IN THE PLAN DOES NOT MATCH THE
 DETAILED PROVIDED AT THE BOTTOM OF SHEET SP-1. THE
 DETAIL MUST MATCH THE SITE PLAN. PLEASE REVISE FOR
 CONSISTENCY. [5/4/2018 REPEAT COMMENT]
  
 5.) BICYCLE PARKING CALCULATIONS INCORRECT. PLEASE
 REVISE. [ZLDR S.94-485(Q)]
  
 6.) PROVIDE A DETAIL OF THE 8 FT. X 15 FT. CANOPY
 STRUCTURE LOCATED BETWEEN OUTDOOR COURTS 1 AND 2. THE
 DETAIL IS STILL MISSING FROM THE PLAN. [5/4/2018 REPEAT
 COMMENT]
  
 7.) SHOW THE LOCATION OF ANY MECHANICAL EQUIPMENT
 PROVIDED FOR THE PROJECT (I.E. ROOFTOP OR GROUND
 LEVEL). ANY MECHANICAL EQUIPMENT SHALL BE SCREENED FROM
 PUBLIC VIEW. [5/4/2018 REPEAT COMMENT]
  
 8.) STRUCTURAL OVERHANGS/DECORATIVE FEATURES SHALL NOT
 PROJECT FARTHER THAN 3 FT. INTO ANY SETBACK. PLEASE
 ILLUSTRATE AND DIMENSION ALL PROJECTIONS FROM THE
 BUILDING (I.E. CANOPIES, ETC.). [5/4/2018 REPEAT
 COMMENT]
  
 9.) REFERENCE THE CODE SECTION FOR THE 0 FT. INTERIOR
 SIDE SETBACK ALLIANCE FOR COMMERCIAL PROPERTIES
 ABUTTING THE RAILROAD TRACK. REFERENCE: ZLDR
 S.94-305(B)(11)] [5/4/2018 REPEAT COMMENT]
  
 10.) PLEASE ADDRESS THE FOLLOWING IN THE SITE DATA
 TABULAR: INCLUDE PROPOSED SQUARE FOOTAGE INFORMATION
 FOR THE REQUIRED ELEMENTS (I.E. IMPERVIOUS/PERVIOUS
 SURFACE AREA, LANDSCAPE AREA, OPEN SPACE AREA, ETC.);
 BUILDING HEIGHT INFORMATION SHOULD INCLUDED THE MAXIMUM
 HEIGHT ALLOWED IN THE DISTRICT AND THE PROPOSED HEIGHT
 OF THE BUILDING; PARKING CALCULATIONS INCORRECT -
 PLEASE REVISE. [5/4/2018 REPEAT COMMENT]
  
 11.) PLEASE ADDRESS THE FOLLOWING IN THE DEVELOPMENT
 REGULATIONS TABULAR: THE MINIMUM BUILDING SIDE SETBACK
 TO THE WEST SEEMS TO BE 10 FT. (NOT 57.1 FT. AS NOTED
 IN THE PLANS). SETBACK MUST BE MEASURED FROM THE
 CLOSEST POINT OF THE BUILDING TO THE PROPERTY LINE.
 [ZLDR S.94-149(2)] [5/4/2018 REPEAT COMMENT]
  
 12.) ONE INTERIOR LANDSCAPE ISLAND SHALL BE REQUIRED
 FOR EVERY TEN (10) PARKING SPACES IN A ROW. THE PARKING
 AREA DOES NOT COMPLY WITH THIS STANDARD. PLEASE
 ADDRESS. [ZLDR S.94-443(C)(3)]
  
 13.) PROVIDE A DETAIL OF THE PROPOSED 6 FT. HIGH WALL
 ALONG THE WESTERN PROPERTY LINE.
  
 14.) THE NOTE REFERENCING THE SURVEY AT THE BOTTOM OF
 SHEET SP-1 IS INCORRECT. PLEASE ADDRESS WITH A NEW
 SURVEY.
  
 15.) REFERENCE TO HPB CASE NO. 18-27 SHALL BE PROVIDED
 IN THE PLANS AS"A NOTE.
  
 16.) THE BUILDING SQUARE FOOTAGE NUMBERS (1ST AND 2ND
 FLOOR) IN THE SITE PLAN DO NOT MATCH THE NUMBERS
 PROVIDED IN THE ARCHITECTURAL PLANS. PLEASE ADDRESS FOR
 CONSISTENCY.
  
  
 LANDSCAPE COMMENTS:
  
 1.) A MINIMUM 5 FT. WIDE LANDSCAPE BUFFER STRIP SHALL
 BE PROVIDED ALONG THE PORTION OF THE EAST PROPERTY LINE
 WHERE THERE IS NO BUILDING AND ABUTS THE RAILROAD ROW.
 [ZLDR S.94-443(B)] [5/4/2018 REPEAT COMMENT]
  
 2.) FINAL LANDSCAPE PLAN SHALL BE SIGNED, DATED AND
 SEALED BY A FLORIDA REGISTERED LANDSCAPE ARCHITECT.
  
 ARCHITECTURAL COMMENTS (FLOOR PLANS AND ELEVATIONS)
  
 1.) ELEVATIONS AND FLOOR PLAN SHALL BE CONSISTENT
 (INCLUDING ALL ACCESS POINTS AND OPENINGS, STRUCTURAL
 OVERHANGS, ETC.). ELEVATIONS SHOW SOME PROJECTIONS THAT
 ARE NOT REFLECTED OR DIMENSIONED IN THE FLOOR PLAN.
 [5/4/2018 REPEAT COMMENT]
  
 2.) DETAILS IN THE CONCEPT FLOOR PLANS (SHEET A-1.01)
 DO NOT MATCH THE DETAILS PROVIDED IN THE REVISED SITE
 PLAN (SHEET SP-1). PLEASE ADDRESS FOR CONSISTENCY.
  
 3.) LOCATION OF THE PROPOSED BICYCLE RACK SHALL BE
 ILLUSTRATED IN THE CONCEPT FLOOR PLANS (SHEET A-1.01).
 THIS IS TO ENSURE THE LOCATION OF THE BICYCLE RACK
 MEETS THE STANDARDS FOR PLACEMENT NEAR THE PRINCIPAL
 ENTRANCE OF THE BUILDING.
  
 4.) THE SQUARE FOOTAGE NUMBERS PROVIDED IN THE
 ARCHITECTURAL PLANS DO NOT MATCH THE SQUARE FOOTAGE
 NUMBERS PROVIDED IN THE SITE PLAN (SHEET SP-1).
  
  
 LIGHTING COMMENTS:
  
 1.) STAFF HAS ACKNOWLEDGED THE CONDITION FROM HISTORIC
 PRESERVATION THAT NO EXTERIOR LIGHTS WILL BE INSTALLED
 FOR THE OUTDOOR COURTS; HOWEVER, WILL THERE BE ANY
 LIGHTING PROVIDED ON THE BUILDING AND/OR ELSEWHERE ON
 THE PROPERTY? IF SO, WHERE WILL THE FIXTURES BE PLACED?
 A PHOTOMETRIC PLAN SHOWING THE ILLUMINATION OF ANY
 LIGHTING ON THE PROPERTY SHALL BE PROVIDED.
  
 2.) PLEASE NOTE THAT ANY/ALL OUTDOOR LIGHTING SHALL BE
 SHIELDED TO REDUCE GLARE AND SHALL BE ARRANGED TO
 REFLECT LIGHT OR GLARE AWAY FROM ALL ADJACENT
 RESIDENTIAL DISTRICTS, ADJACENT RESIDENCES OR PUBLIC
 THOROUGHFARES. A NOTE SHALL BE PROVIDED IN THE
 PHOTOMETRIC PLAN TO ADDRESS COMPLIANCE. [5/4/2018
 REPEAT COMMENT]
  
  
 SIGNAGE COMMENTS:
  
 1.) AT MINIMUM, THERE SHOULD BE A NOTE PROVIDED IN THE
 PLANS STATING THAT "WALL SIGNAGE WILL BE ADDRESSED AT
 TIME OF BUILDING PERMIT AND SHALL COMPLY WITH THE SIGN
 REQUIREMENTS OF THE RTD DISTRICT PER ZONING AND LAND
 DEVELOPMENT REGULATIONS, SECTION 94-149(13)." PLEASE
 NOTE THAT PER ZLDR S.94-149(13)(B.), ONLY ONE WALL
 SIGN, NOT TO EXCEED THE LESSER OF ONE PERCENT OF GROSS
 WALL AREA OR 16 SQ. FT. SHALL BE PERMITTED. ACCORDING
 TO THE ELEVATIONAL DRAWINGS, A TOTAL OF TWO (2) SIGNS,
 WHICH LOOKS TO EXCEED THE SIGN AREA REQUIREMENTS, HAVE
 BEEN PROVIDED.
  
 2.) DEMONSTRATE THAT THE PROPOSED MONUMENT SIGN WILL
 NOT OBSTRUCT VIEW BY ILLUSTRATING THE 20 FT. BY 20 FT.
 VISIBILITY TRIANGLE, PURSUANT TO ZLDR S.94-305(E).
  
 3.) ARE THERE SUPPOSED TO BE MULTIPLE MONUMENT SIGNS ON
 THE PROPERTY? SIGN DETAIL ON SHEET SP-1 SHOWS THAT THE
 SIGN DETAIL IS DETAIL "A". PLEASE CLARIFY.
  
  
 INSTRUCTIONS FOR RESUBMITTAL:
  
 * PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF
 FIFTEEN (15) PAPER COPIES, ONE (1) REDUCED COPY IN 8.5
 INCHES X 11 INCHES AND ONE (1) SET IN 11 INCHES X 17
 INCHES, AND AN ELECTRONIC COPY OF ALL PLANS.
  
 * CHANGES ON THE RESUBMITTED PLANS MAY RESULT IN
 ADDITIONAL COMMENTS.
  
 * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NOT ADDITIONAL COST. IF
 PREVIOUSLY-ISSUED COMMENTS CONTINUE TO NOT BE
 SUFFICIENTLY ADDRESSED, THE APPLICANT WILL BE ASSESSED
 A RESUBMITTAL FEE. SUCH FEE WILL BE 20 PERCENT OF THE
 ORIGINAL APPLICATION FEE ($200.00).
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
  