| 2018-04-10 20:44:56 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. |
| | |
| | 2. FOR ANY BUILDING CROSSING A PROPERTY LINE, EITHER A |
| | RECORDED UNITY OF TITLE, OR SOME OTHER APPROVED LEGAL |
| | INSTRUMENT, SHALL BE INCLUDED WITH THE PERMIT |
| | APPLICATION, OR THE BUILDING MUST HAVE A FIRE WALL |
| | ALONG THE PROPERTY LINE, PER SECTION 202 OF FLORIDA |
| | BUILDING CODE, BUILDING, FIRE SEPARATION DISTANCE. |
| | |
| | 3. NUMBER OF ACCESSIBLE PARKING SPACES SERVING THE |
| | OFFICE SPACE. THERE ARE NOT SUFFICIENT ACCESSIBLE |
| | PARKING SPACES DIRECTLY SERVING THE OFFICE SPACE. THE |
| | PARKING TABLE ON SITE AND PROJECT DATA SHEET A0.01 |
| | STATES THAT 562 PARKING SPACES ARE PROPOSED FOR THE |
| | OFFICE USE. THEREFORE 13 ACCESSIBLE PARKING SPACES ARE |
| | REQUIRED FOR OFFICE USE PER SECTION 208.2 OF FLORIDA |
| | ACCESSIBILITY CODE. OFFICE LEVEL PLAN SHEETS A1.09, |
| | A1.10, AND A1.11 FOR LEVELS 9 THROUGH 18 ALL SHOW THAT |
| | ONLY ELEVATORS 1 THROUGH 5 SERVE THE OFFICE LEVELS. |
| | ONLY 4 OF THE PROVIDED ACCESSIBLE PARKING SPACES ARE |
| | LOCATED AS THE CLOSEST PARKING SPACES TO THOSE |
| | ELEVATORS. OF THOSE 4 ACCESSIBLE PARKING SPACES, 2 ARE |
| | ON LEVEL 7 PLAN SHEET A1.07 AND 2 ARE ON LEVEL 8 PLAN |
| | SHEET A1.08. THE REMAINDER OF THE ACCESSIBLE PARKING |
| | SPACES ARE SHOWN ON PLAN SHEETS A1.02 THOUGH A1.06, FOR |
| | LEVELS 2 THROUGH 6, AND NONE OF THOSE ARE THE CLOSEST |
| | PARKING SPACES TO ELEVATORS 1 THROUGH 5. SO, THERE ARE |
| | NOT ENOUGH ACCESSIBLE PARKING SPACES SERVING THE OFFICE |
| | SPACE. IT IS NOTED THAT ELEVATORS 1 THROUGH DO NOT STOP |
| | AT LEVELS 2 THROUGH 6 BUT THAT DOES NOT AFFECT THIS |
| | ISSUE. PER SECTION 208.3 OF FLORIDA ACCESSIBILITY CODE, |
| | ACCESSIBLE PARKING SPACES ARE TO BE LOCATED ON THE |
| | SHORTEST POSSIBLE ROUTE OF TRAVEL FROM ADJACENT PARKING |
| | TO AN ACCESSIBLE ENTRANCE. THE DESIGN OF ACCESSIBLE |
| | PARKING SPACES SHALL COMPLY WITH SECTION 502 OF FLORIDA |
| | ACCESSIBILITY CODE |
| | |
| | 4. VAN ACCESSIBLE PARKING SPACES. A TOTAL OF 3 VAN |
| | ACCESSIBLE PARKING SPACES ARE REQUIRED BUT ONLY 2 ARE |
| | SHOWN. LEVEL 2 PLAN SHEET A1.02 SHOWS 2 VAN ACCESSIBLE |
| | PARKING SPACES AND THERE DOES NOT APPEAR TO BE ANY |
| | OTHERS SHOWN ON THE PLANS, SO AN ADDITIONAL VAN |
| | ACCESSIBLE PARKIG SPACE IS REQUIREDPER SECTION 208.2.4 |
| | OF FLORIDA ACCESSIBILITY CODE, ONE IN EVERY SIX |
| | REQUIRED ACCESSIBLE SPACES (AT LEAST ONE) IN A PARKING |
| | STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND DESIGNED IN |
| | ACCORDANCE WITH SECTION OF 502 OF FLORIDA ACCESSIBILITY |
| | CODE (VERTICAL CLEARANCE NOT LESS THAN 98 INCHES AT |
| | SPACE AND VEHICULAR ACCESS ROUTE). |
| | |
| | 5. EGRESS FROM THE SOUTH OFFICE SPACE ON LEVEL 2 AND |
| | LEVEL 4. EGRESS FROM THE OFFICE SPACE SHALL NOT PASS |
| | THROUGH THE PARKING GARAGE. LEVEL 2 PLAN SHEET A1.02 |
| | AND LEVEL 4 PLAN SHEET A1.04 SHOW ONE OF THE EGRESS |
| | PATHS FROM THE SOUTH (FERN ST) OFICE SPACE GOING |
| | THROUGH THE PARKING GARAGE. SECTION 1016.2(2) OF |
| | FLORIDA BUILDING CODE STATES THAT EGRESS FROM A SPACE |
| | SHALL NOT PASS THROUGH AN ADJOINING AREA UNLESS SUCH |
| | ADJOINING AREA AND THE SPACE SERVED ARE ACCESSORY TO |
| | ONE OR THE OTHER. |
| | |
| | 6. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, |
| | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR |
| | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, |
| | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE |
| | FLORIDA BUILDING CODE. |
| | |
| | 7. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND |
| | OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT, |
| | COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF |
| | OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF |
| | CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE |
| | VERIFIED. |
| | |
| | 8. ENCLOSED PARKING GARAGES. THE PARKING GARAGE APPEARS |
| | TO BE ENCLOSED AND MECHANICALLY VENTILATED. IF THE |
| | PARKING GARAGE DOES NOT HAVE WALL OPENINGS, OR |
| | SUFFICIENT WALL OPENINGS TO MEET THE DEFINITION OF AN |
| | OPEN PARKING GARAGE, IT WILL BE CONSIDERED AN ENCLOSED |
| | PARKING GARAGE AND MUST HAVE EXHAUST SYSTEMS. THE |
| | EXHAUST SYSTEMS SHALL BE DESIGNED TO MINIMIZE NOISE |
| | LEVELS USING INLINE FAN SILENCERS OR OTHER APPROVED |
| | METHODS. |
| | |
| | 9. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS |
| | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE |
| | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED |
| | FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, |
| | FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, |
| | GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, |
| | SITE IRRIGATION, ETC. |
| | |
| | 10. EACH SEPARATE BUILDING, AND UNIT WITH AN |
| | INDEPENDENT ENTRANCE FROM THE STREET, SHALL HAVE A |
| | SEPARATE ADDRESS. FOR STREET ADDRESSING, CONTACT |
| | MICHAEL ORIO, GIS SUPPORT SPECIALIST, AT (561) 494 |
| | 1080, OR BY EMAIL: [email protected] |
| | |
| | 11. THIS PROJECT WILL BE SUBJECT TO ART IN PUBLIC |
| | PLACES (AIPP) ASSESSMENT. FOR ADVICE ON THE PROVISION |
| | OF PUBLIC ARTWORK IN LIEU OF THE AIPP ASSESSMENT, |
| | CONTACT SYBILLE WELTER, ART IN PUBLIC PLACES |
| | COORDINATOR, AT (561) 822-1521, OR BY EMAIL: |
| | [email protected] |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |
Print |